Table 101 — Hilti HIT-HY 200 A / R V3 allowable adhesive bond loads for threaded rods and reinforcing bars in the top of grout-filled concrete masonry walls 1 , 2 , 3 , 4 , 5 , 6 , 7
Nominal anchor diameter or rebar size
1 / 2 "
5 / 8 "
# 4
# 5
Effective embedment in . ( mm )
Edge distance in . ( mm ) 8
Minimum end distance in . ( mm )
Tension lb ( kN )
Load parallel to edge of masonry wall
Shear load lb ( kN ) 9
Load perpendicular to edge of masonry wall
1 3 / 4 685 775 285 4 -1 / 2 ( 44 ) ( 3.0 ) ( 3.4 ) ( 1.3 ) ( 114 ) 4 880 1,156 480 ( 102 ) ( 3.9 ) ( 5.1 ) ( 2.1 ) 1 3 / 4 830 890 315 5 -5 / 8 ( 44 ) 8 ( 3.7 ) ( 4.0 ) ( 1.4 ) ( 143 ) 4 ( 203 ) 980 1,315 625
( 102 ) ( 4.4 ) ( 5.8 ) ( 2.8 ) 4 -1 / 2 770 605 235 ( 114 ) 1 3 / 4 ( 3.4 ) ( 2.7 ) ( 1.0 ) 5 -5 / 8 ( 44 ) 795 720 295 ( 143 ) ( 3.5 ) ( 3.2 ) ( 1.3 )
1 All values are for anchors installed in fully grouted concrete masonry with minimum masonry prism strength of 1,500 psi . Concrete masonry units shall be lightweight , medium-weight or heavy-weight conforming to ASTM C90 . Allowable loads are calculated using a safety factor of 5 .
2 When using the basic load combinations in accordance with IBC Section 1605.3.1 or the alternative basic load combinations in IBC Section 1605.3.2 . Tabulated allowable loads must not be increased for seismic or wind loading . 3 One anchor shall be permitted to be installed in each concrete block . 4 Anchors are not permitted to be installed in a head joint , flange or web of the concrete masonry unit . 5 Allowable loads must be the lesser of the adjusted masonry or bond tabulated values and the steel values given in tables 102 and 103 . 6 Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with figure 14 . 7 For combined loading : ( T applied
/ T allowable ) + ( V applied
/ V allowable
) ≤ 1 8 The tabulated edge distance is measured from the anchor centerline to the edge of the concrete block . See figure below . 9 Linear interpolation of load values between the two tabulated edge distances is permitted .
Hilti HIT-HY 200 A / R V3 specifications for HAS threaded rod in grout-filled masonry walls
Edge and end distances for threaded rods and reinforcing bars installed in the top of grout-filled CMU
1-3 / 4 " Edge Distance
Threaded Rod or Reinforcing Bar
End Distance
100 Anchor Fastening Technical Guide Edition 22 | 3.0 ANCHORING SYSTEMS | 3.2.2 HILTI HIT-HY 200 A / R V3 Hilti , Inc . 1-800-879-8000 | en español 1-800-879-5000 | www . hilti . com | Hilti ( Canada ) Corporation | www . hilti . ca | 1-800-363-4458