3.0 MODULAR SUPPORT SYSTEM 3.2.3 MT SYSTEM CONNECTORS MT-C-T 3D / 2
Description
Two-sided 3D connector for channel. |
Material Specifications |
Standard 1 |
Grade 1 |
F y
, ksi( MPa)
|
F u
, ksi( MPa)
|
GB / T 1591 |
Q355 B |
51.49( 355) |
68.17( 470) |
1. Mechanical properties of GB / T 1591 Grade Q355 B meet or exceed the mechanical properties of ASTM A1011 SS Grade 50.
Corrosion Protection
Electro-Galvanized( EG)
MT-C-T 3D / 2
Hot-Dipped Galvanized( HDG)
MT-C-T 3D / 2 OC
Ordering Information
Description
Weight Per Piece lbs( kg)
Quantity Piece( s)
Item No.
MT-C-T 3D / 2 0.92( 0.42) 10 2272058 MT-C-T 3D / 2 OC 0.92( 0.42) 10 2272059
�����“)
���
� ����“)
����
������“)
mm( in)
����
������“)
Figure 36- MT Channel Connection
Table 129- Allowable Strength Design( ASD) Load Data 1, 2, 3, 4
F z lb( kN)
1,010( 4.50)
1. Minimum safety factor, Ω, for tabulated values is 2.65. 2. Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD) values. 3. See Figure 36. 4. Tabulated values represent the maximum total allowable load of the connector. The applied load on a single horizontal leg cannot exceed 875 lbs( 3.91 kN).
Table 130- Limit State Design( LSD) Load Data 1, 2, 3
A. MT-30 / 50 / 60 / 40D
Figure 37- MT Channel Connection
F z lb( kN)
1,405( 6.26)
1. Maximum resistance factor, Φ, for tabulated values is 0.55. 2. See Figure 36. 3. Tabulated values represent the maximum total factored load of the connector. The applied load on a single horizontal leg cannot exceed 1,245 lbs( 5.54 kN).
Table 131- Allowable Strength Design( ASD) Load Data 1, 2, 3, 4
F z lb( kN)
1,010( 4.50)
1. Minimum safety factor, Ω, for tabulated values is 2.65. 2. Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD) values. 3. See Figure 37. 4. Tabulated values represent the maximum total allowable load of the connector. The applied load on a single horizontal leg cannot exceed 570 lbs( 2.54 kN).
Table 132- Limit State Design( LSD) Load Data 1, 2, 3
2023 |
A. MT-30 / 50 / 60 / 40D |
F z lb( kN)
1,405( 6.26)
1. Maximum resistance factor, Φ, for tabulated values is 0.55. 2. See Figure 37. 3. Tabulated values represent the maximum total factored load of the connector. The applied load on a single horizontal leg cannot exceed 805 lbs( 3.60 kN).
|