Post-Installed Anchors in Masonry US English | Page 49

Table 24. Hilti HIT-HY 270 design strength with clay brick failure modes for threaded rods not near an edge in uncracked, clay brick 1, 2, 3, 4, 5, 6
Nominal anchor diameter in.
1 / 4
5 / 16
3 / 8
1 / 2
Effective embedment in.( mm)
3-1 / 8( 79)
3-1 / 8( 79)
3-1 / 8( 79)
3-1 / 8( 79)
Tension— ϕN n f ́m = 3000 psi( 20.7 MPa) lb( kN)
300( 1.3)
470( 2.1)
470( 2.1)
560( 2.5)
Shear— ϕV n f ́m = 3000 psi( 20.7 MPa) lb( kN)
460( 2.0)
625( 2.8)
625( 2.8)
1,350
( 6.0) 1 Tabular values are for a single anchor with no influence from nearby edges or additional anchors. For designs with
the influence of nearby edges or additional anchors, use Hilti PROFIS Engineering Design software or perform anchor calculation using design equations from AC58. 2 Compare masonry tabular values to the steel values in the Appendix. The lesser of the values is to be used for the design. 3 LFRD load capacities based on evaluation in accordance with AC58. 4 Data is for Temperature Range A: Maximum short-term temperature = 130 ° F( 55 ° C) | Maximum long-term temperature
= 110 ° F( 43 ° C). For Temperature Range B: Maximum short-term temperature = 176 ° F( 80 ° C) | Maximum long-term temperature = 110 ° F( 43 ° C), multiply design strength values by 0.62. 5 Tabular values are for dry masonry conditions. For water saturated masonry conditions, multiply design strength values by:
α sat, 1 / 4-in, 5 / 16-in and 3 / 8-in diameter- α sat = 0.48 1 / 2-in diameter- α sat = 0.71 6 Tabular values are for static loads only. Seismic design is not permitted.
Table 25. Hilti HIT-HY 270 design strength with clay brick failure modes for threaded rods not near an edge in cracked, clay brick 1, 2, 3, 4, 5, 6
Nominal anchor diameter in.
1 / 4
5 / 16
3 / 8
Effective embedment in.( mm)
3-1 / 8( 79)
3-1 / 8( 79)
3-1 / 8( 79)
Tension— ϕN n f ́m = 3000 psi( 20.7 MPa) lb( kN)
150( 0.7)
235( 1.0)
235( 1.0)
Shear— ϕV n f ́m = 3000 psi( 20.7 MPa) lb( kN)
460( 2.0)
625( 2.8)
625( 2.8)
3-1 / 8 280
1,350 1 / 2
( 79)( 1.2)
( 6.0) 1 Tabular values are for a single anchor with no influence from nearby edges or additional anchors. For designs with
the influence of nearby edges or additional anchors, use Hilti PROFIS Engineering Design software or perform anchor calculation using design equations from AC58. 2 Compare masonry tabular values to the steel values in the Appendix. The lesser of the values is to be used for the design. 3 LFRD load capacities based on evaluation in accordance with AC58. 4 Data is for Temperature Range A: Maximum short-term temperature = 130 ° F( 55 ° C) | Maximum long-term temperature
= 110 ° F( 43 ° C). For Temperature Range B: Maximum short-term temperature = 176 ° F( 80 ° C) | Maximum long-term temperature = 110 ° F( 43 ° C), multiply design strength values by 0.62. 5 Tabular values are for dry masonry conditions. For water saturated masonry conditions, multiply design strength values by: α sat, 1 / 4-in, 5 / 16-in, and 3 / 8-in diameter- α sat = 0.48 1 / 2-in diameter- α sat = 0.71 6 Tabular values are for static loads only. Seismic design is not permitted.
Table 26. Hilti HIT-HY 270 design strength with clay brick failure modes for HIT-IC inserts not near an edge in uncracked, clay brick 1, 2, 3, 4, 5, 6
Nominal anchor diameter in.
5 / 16
3 / 8
1 / 2
Effective embedment in.( mm)
3-1 / 8( 79)
3-1 / 8( 79)
3-1 / 8( 79)
Tension— ϕN n
f ́m = 3000 psi( 20.7 MPa) lb( kN)
145( 0.6)
145( 0.6)
205( 0.9)
Shear— ϕV n
f ́m = 3000 psi( 20.7 MPa) lb( kN)
450( 2.0)
450( 2.0)
1,305
( 5.8) 1 Tabular values are for a single anchor with no influence from nearby edges or additional anchors. For designs with
the influence of nearby edges or additional anchors, use Hilti PROFIS Engineering Design software or perform anchor calculation using design equations from AC58. 2 Compare masonry tabular values to the steel values in the Appendix. The lesser of the values is to be used for the design. 3 LFRD load capacities based on evaluation in accordance with AC58. 4 Data is for Temperature Range A: Maximum short-term temperature = 130 ° F( 55 ° C) | Maximum long-term temperature
= 110 ° F( 43 ° C). For Temperature Range B: Maximum short-term temperature = 176 ° F( 80 ° C) | Maximum long-term temperature = 110 ° F( 43 ° C), multiply design strength values by 0.62. 5 Tabular values are for dry masonry conditions. For water saturated masonry conditions, multiply design strength values by:
α sat, 5 / 16-in and 3 / 8-in diameter- α sat = 0.57 1 / 2-in diameter- α sat = 0.71 6 Tabular values are for static loads only. Seismic design is not permitted.
Table 27. Hilti HIT-HY 270 design strength with clay brick failure modes for HIT-IC inserts not near an edge in cracked, clay brick 1, 2, 3, 4, 5, 6
Nominal anchor diameter in.
5 / 16
3 / 8
1 / 2
Effective embedment in.( mm)
3-1 / 8( 79)
3-1 / 8( 79)
3-1 / 8( 79)
Tension— ϕN n
f ́m = 3000 psi( 20.7 MPa) lb( kN)
70( 0.3)
70( 0.3)
100( 0.4)
Shear— ϕV n
f ́m = 3000 psi( 20.7 MPa) lb( kN)
450( 2.0)
450( 2.0)
1,305
( 5.8) 1 Tabular values are for a single anchor with no influence from nearby edges or additional anchors. For designs with
the influence of nearby edges or additional anchors, use Hilti PROFIS Engineering Design software or perform anchor calculation using design equations from AC58. 2 Compare masonry tabular values to the steel values in the Appendix. The lesser of the values is to be used for the design. 3 LFRD load capacities based on evaluation in accordance with AC58. 4 Data is for Temperature Range A: Maximum short-term temperature = 130 ° F( 55 ° C) | Maximum long-term temperature
= 110 ° F( 43 ° C). For Temperature Range B: Maximum short-term temperature = 176 ° F( 80 ° C) | Maximum long-term temperature = 110 ° F( 43 ° C), multiply design strength values by 0.62. 5 Tabular values are for dry masonry conditions. For water saturated masonry conditions, multiply design strength values by:
α sat, 5 / 16-in and 3 / 8-in diameter- α sat = 0.57 1 / 2-in diameter- α sat = 0.71 6 Tabular values are for static loads only. Seismic design is not permitted.
49