Table 16 — Hilti HIT-HY 200 V3 adhesive design strength with masonry / bond failure for HIS- ( R ) N in the face of uncracked fully grouted CMU walls and installed at minimum distance from centerline of hollow head joint 1 , 2 , 3 , 4 , 5 , 6 , 7 , 8
Nominal anchor diameter in .
3 / 8
1 / 2
Effective embedment in . ( mm ) f ́m = 1500 psi ( 10.3 MPa ) lb ( kN )
Tension ( lesser of breakout or bond ) — ΦN n
f ́m = 2000 psi ( 13.8 MPa ) lb ( kN ) f ́m = 2500 psi ( 17.2 MPa ) lb ( kN ) f ́m = 3000 psi ( 20.7 MPa ) lb ( kN )
Shear ( lesser of breakout , pryout , or crushing ) - ΦV n
f ́m = 1500 psi ( 10.3 MPa ) lb ( kN ) f ́m = 2000 psi ( 13.8 MPa ) lb ( kN ) f ́m = 2500 psi ( 17.2 MPa ) lb ( kN ) f ́m = 3000 psi ( 20.7 MPa ) lb ( kN )
4-3 / 8 |
1,395 |
1,395 |
1,395 |
1,395 |
1,520 |
1,755 |
1,965 |
2,150 |
( 111 ) |
( 6.2 ) |
( 6.2 ) |
( 6.2 ) |
( 6.2 ) |
( 6.8 ) |
( 7.8 ) |
( 8.7 ) |
( 9.6 ) |
5 |
2,295 |
2,650 |
2,935 |
2,935 |
1,665 |
1,925 |
2,150 |
2,360 |
( 127 ) |
( 10.2 ) |
( 11.8 ) |
( 13.1 ) |
( 13.1 ) |
( 7.4 ) |
( 8.6 ) |
( 9.6 ) |
( 10.5 ) |
1 Linear interpolation between embedment depths and masonry compressive strengths is not permitted .
2 Tabular values are for a single anchor located 2-in from centerline of a hollow head joint with no additional influence from nearby edges or additional anchors . For designs with the influence of nearby edges , different distances to a hollow head joint , or additional anchors , use Hilti PROFIS Engineering Design software or perform anchor calculation using design equations from AC58 . 3 Compare masonry tabular values to the steel values in the Appendix . The lesser of the values is to be used for the design . 4 The maximum embedment for a 8-in CMU block is 6-3 / 4-in . The maximum embedment for a 10-in CMU block is 8-in . The maximum embedment for a 12-in CMU block is 10-in . 5 Data is for Temperature Range A : Maximum short term temperature = 130 ° F ( 55 ° C ) | Maximum long term temperature = 110 ° F ( 43 ° C ).
For Temperature Range B : Maximum short term temperature = 176 ° F ( 80 ° C ) | Maximum long term temperature = 110 ° F ( 43 ° C ), multiply design strength values by 0.82 . 6 Tabular values are for dry masonry conditions . For water saturated masonry conditions , multiply design strength values by α sat
3 / 8-in and 1 / 2-in diameter - α sat
= 0.65 7 Tabular values are for static loads only . Seismic design is not permitted for uncracked masonry . 8 Tabular values are for short term loads only . For sustained loads including overhead use , see Section 3.0 .
Table 17 — Hilti HIT-HY 200 V3 adhesive design strength with masonry / bond failure for HIS- ( R ) N in the face of cracked fully grouted CMU walls and installed at minimum distance from centerline of hollow head joint 1 , 2 , 3 , 4 , 5 , 6 , 7 , 8
Nominal anchor diameter in .
3 / 8
1 / 2
Effective embedment in . ( mm ) f ́m = 1500 psi ( 10.3 MPa ) lb ( kN )
Tension ( lesser of breakout or bond ) — ΦN n
f ́m = 2000 psi ( 13.8 MPa ) lb ( kN ) f ́m = 2500 psi ( 17.2 MPa ) lb ( kN ) f ́m = 3000 psi ( 20.7 MPa ) lb ( kN )
Shear ( lesser of breakout , pryout , or crushing ) - ΦV n
f ́m = 1500 psi ( 10.3 MPa ) lb ( kN ) f ́m = 2000 psi ( 13.8 MPa ) lb ( kN ) f ́m = 2500 psi ( 17.2 MPa ) lb ( kN ) f ́m = 3000 psi ( 20.7 MPa ) lb ( kN )
4-3 / 8 |
1,040 |
1,040 |
1,040 |
1,040 |
1,085 |
1,255 |
1,405 |
1,535 |
( 111 ) |
( 4.6 ) |
( 4.6 ) |
( 4.6 ) |
( 4.6 ) |
( 4.8 ) |
( 5.6 ) |
( 6.2 ) |
( 6.8 ) |
5 |
1,620 |
1,870 |
2,090 |
2,290 |
1,190 |
1,375 |
1,535 |
1,685 |
( 127 ) |
( 7.2 ) |
( 8.3 ) |
( 9.3 ) |
( 10.2 ) |
( 5.3 ) |
( 6.1 ) |
( 6.8 ) |
( 7.5 ) |
1 Linear interpolation between embedment depths and masonry compressive strengths is not permitted .
2 Tabular values are for a single anchor located 2-in from centerline of a hollow head joint with no additional influence from nearby edges or additional anchors . For designs with the influence of nearby edges , different distances to a hollow head joint , or additional anchors , use Hilti PROFIS Engineering Design software or perform anchor calculation using design equations from AC58 . 3 Compare masonry tabular values to the steel values in the Appendix . The lesser of the values is to be used for the design . 4 The maximum embedment for a 8-in CMU block is 6-3 / 4-in . The maximum embedment for a 10-in CMU block is 8-in . The maximum embedment for a 12-in CMU block is 10-in . 5 Data is for Temperature Range A : Maximum short term temperature = 130 ° F ( 55 ° C ) | Maximum long term temperature = 110 ° F ( 43 ° C ).
For Temperature Range B : Maximum short term temperature = 176 ° F ( 80 ° C ) | Maximum long term temperature = 110 ° F ( 43 ° C ), multiply design strength values by 0.82 . 6 Tabular values are for dry masonry conditions . For water saturated masonry conditions , multiply design strength values by α sat
3 / 8-in and 1 / 2-in diameter - α sat
= 0.65 7 Tabular values are for static loads only . For seismic loads , multiply design strength values in tension and shear by α seis
3 / 8-in diameter - α seis = 0.58
1 / 2-in diameter - α seis
= 0.75 8 Tabular values are for short term loads only . For sustained loads including overhead use , see Section 3.0 .
30 Masonry Fastening Technical Guide Edition 24 | 7.0 HIT-HY 200 V3 HYBRID FOR MASONRY CONSTRUCTION Hilti , Inc . 1-800-879-8000 | en español 1-800-879-5000 | www . hilti . com | Hilti ( Canada ) Corporation | www . hilti . ca | 1-800-363-4458