METASYS
HVAC
BUILDING MANAGEMENT
SYSTEM CONTROL PRODUCTS
PROGRAMMABLE CONTROLLERS RM METASYS CONTROLLERS
ORDERING INFORMATION
POINT TYPES , FUNCTIONS AND RATINGS POINT TYPES FUNCTION
Analog IN
Binary IN
Analog OUT
Binary OUT
Lock man Op .
Analog Input , Voltage mode Analog Input , Current mode
Analog Input , Resistive mode
Binary Input , Dry contact maintained mode
Analog Output , Voltage mode , sources 0-10 VDC output voltage
Binary Output , up to 250VAC Relay contact Connects NO to common when activated
Binary Output , up to 250VAC Relay contact Disconnects NC from Common when activated
Remote lock of manual overrides
SIGNAL / RATING Accepts a 0-10VDC input signal , internal 75kΩ pull-down Accepts a 0-20 mA input signal , internal 100Ω load impedance
Accepts a 0-600 kΩ input signal , internal 12V , 15kΩ pull-up RTD : 1k Nickel [ L & G ], 1k Nickel [ DIN ], 1k Platinum , A99B Silicon Temperature sensor
0.01s minimum pulse width ( 50Hz at 50 % duty cycle ) Internal 35V , 2.7kΩ pull-up
External 1kΩ minimum load required 10 VDC maximum output voltage , 10 mA maximum output current
Characteristics ( Resistive Load ): Initial contact resistance 100mΩ ( at 1A / 24VDC ) Rated load 5A at 250VAC , 5A at 30VDC , 10A at 125VAC Max . switching voltage 277VAC , 30VDC Max . switching capacity 1250VA ( AC ), 150W ( DC ) Endurance 1x10 5 ops ( Rated Load ), 1x10 7 ops ( no Load )
Characteristics ( Resistive Load ): Initial contact resistance 100mΩ ( at 1A / 24 VDC ) Rated load 3A at 250VAC , 5A at 30VDC , 10A at 125VAC Max . switching voltage 277VAC , 30VDC Max . switching capacity 1250VA ( AC ), 150W ( DC ) Endurance 1x10 5 ops ( Rated Load ), 1x10 7 ops ( no Load )
Binary Input , Dry Contact Maintained Mode 0.01 s minimum pulse width ( 50 Hz at 50 % duty cycle ) Internal 35 V , 2.7kΩ pull-up
119 European Products Catalogue 2021