Lubezine Volume 8 * NOVEMBER 2013 - JANUARY 2014 | Page 22

RECYCLING FEATURE insulation. (See figure 2). Indefinite life The cellulose materials are the weakest link in the insulation system. Since the life of the transformer is actually the life of the cellulose insulation and degradation of the cellulose is irreversible, the decay products should be removed before they can do any further damage to the cellulose. With proper maintenance, the cellulose can virtually have an indefinite life. To test for furanics, a sample of the oil is obtained and certain chemical techniques are used to extract the furans from the oil. The extract is then analysed using a process called high performance liquid chromatography (HPLC). The results are usually reported in terms of parts per billion (ppb). Dissolved Gas Analysis (DGA) The analysis of gases from petroleum products has been performed for decades using gas chromatography. However, this technique was not applied specifically to transformer mineral oils until the late 1960s/early 1970,s and is now commonly called dissolved gas-inoil analysis (DGA). DGA has become a standard in the electrical maintenance industry throughout the world and is considered to be the most important oil test for transformer oils in electrical apparatus. More importantly, an oil sample can be taken at any time from most equipment without having to take it out of service, allowing a “window” inside the electrical apparatus that helps with diagnosing and trouble-shooting potential problems. As the insulating materials of a transformer break down from excessive thermal or electrical stress, gaseous by-products form. The by-products are characteristic of the type of incipient-fault condition, the materials involved and the severity of the condition. Indeed, it is the ability to detect such a variety of problems that makes this test such a powerful tool for detecting incipient-fault conditions and for root-cause investigations after failures have occurred. Dissolved gases are detectable in low concentrations (ppm level), which usually permit early intervention before failure of the electrical apparatus occurs, and allow for planned maintenance. The DGA technique involves extracting or stripping the gases from the oil and injecting them into a gas chromatograph (GC). Typical gases generated from mineral oil / cellulose (paper and pressboard) -insulated transformers include: Hydrogen, H2; Methane, CH4;Ethane, C2H6; Ethylene, C2H4;Acetylene, C2H2;Carbon Monoxide, CO and Carbon Dioxide, CO2. Additionally, oxygen and nitrogen are always present, their concentrations vary with the type of preservation system used on the transformer. Also, gases such as propane, butane, butene and others can be formed as well, but their use for diagnostic purposes is not widespread. The concentration of the different gases provides information about the type of incipientfault condition present as well as the severity. For example, four broad categories of fault conditions have been described and characterized in Table 1. The severity of an incipient-fault condition is ascertained by the total amount of combustible gases present (CO, H2, C2H2, C2H4, C2H6, CH4) and their rate of generation. Generally, transformers will retain a large portion of the gases generated and therefore produce a cumulative history of the insulating materials’ degradation. This is an important tool for detecting and trending incipient problems. However, it also means that care is needed in interpreting values for a first-time analysis on service-aged transformers (more than several years old), which could contain residual gases from previous events. Abnormal behaviour Some gas generation is expected from normal ageing of the transformer insulation and it is therefore important to differentiate between normal and excessive gassing rates. Normal ageing or gas generation varies with transformer design, loading and type of insulating materials. Routinely, general gassing rates for all transformers are used to define abnormal behaviour. Specific information for a family of transformers can be used when sufficient dissolved gas-in-oil data are available. Acetylene is considered to be the most significant gas generated. An enormous amount of energy is required to produce acetylene, which is formed from the breakdown of oil at temperatures in excess of 700°C. Excessively high overheating of the oil will produce the gas in low concentrations. However, higher concentrations are typically symptomatic of sustained arcing, a more serious operational issue that can cause a transformer failure if left unchecked. DGA is used not only as a diagnostic tool but also to stem apparatus failure. Failure of a large power transformer not only results in the loss of very expensive equipment but it can cause significant collateral damage as well. Revenue losses due to operational outages may be the least worrisome consequence of a failure. Replacement of that transformer can take up to a year if the failure is not catastrophic and can result in tremendous revenue losses. If the failure is catastrophic, then additional losses could be realised, such as adjacent transformers, environmental problems from the release of oil, (which could be as much as 20,000 litres), and the resulting fire that must be contained and smothered. In order to avoid such a failure H