AIRAH Common Equations 1 kWh = 3.6 MJ WATER kW = 4.187 x (L/s) x ∆T(K) kWh = 4.187 x L x ∆T(K) / 3600 where: 4.187 = Specific heat capacity of water (k J/kg K @ 14°C) HEAT CONTENT OF AIR Latent Watt = Watt = where: 2450 = 0.845 = Sensible Watt = Watt = where: 1.025 = Total Watt = where: 1.184 = (2450 k J/kg / 0.845 m³ /kg) x (L/s / 1000) x g/kg 2.900 x L/s x g/kg Latent heat of water (kJ/kg @ 21°C) Specific volume of moist air (m³/kg) (1.025 k J/kg K / 0.845 m³/kg) x L/s x ∆T(K) 1.213 x L/s x ∆T(K) Specific heat of moist air k J/kg.K 1.184 x L/s x (kJ/kg) Density of moist air @ 20°C and 50% RH (kg/m³) POWER – GENERAL EQUATION kW where: ρ h ç Q = 9.81 x h x ρ x Q / 1000 x ç = = = = Density (kg/m3) liquid column height (m)   Note: h = kPa / 9.81 (m) efficiency (where 0 ≤ ç ≤ 1) Flow rate (L/s) Note:  P = 9.81 x h x ρ = Pressure (Pa) POWER – FAN AND PUMP kW = kPa x Q 1000 x η W = ( 9.81 x h x r x Q ) / 1000 x η POWER SHAFT kW = {2 π x r.p.s. x torque (Nm)} / 1000 187