Penetrating Item ( s ) F-Rating T-Rating L-Rating W-Rating Product
METALLIC PENETRANTS IN CONCRETE FLOORS / WALLS ( CONTINUED )
Max . 6 ” steel or cast iron ( with mineral fiber pipe |
|
|
insulation ) ( 6 ” concrete floor ) |
2 Hr |
◼ |
Max . 6 ” steel , cast iron , steel conduit , copper or 4 ” |
EMT ( 6 ”” to 12 ” Concrete ) |
|
Max . 4 ” steel , cast iron , steel conduit , copper or
EMT ( 6 ”” to 12-1 / 2 ” Hollow Core )
|
3 Hr
◼ ◼
|
Tub Box with nom . 1-1 / 2 ” or 2 ” steel pipe with waste / overflow fittings |
3 Hr |
Nom . 3 ” or 4 ” steel or cast iron ( with mineral fiber |
|
|
pipe insulation ) ( 6 ” concrete floor ) |
2 Hr |
◼ |
Max . 10 ” steel or cast iron pipe ( 6 ” concrete floor )
Max . 4 ” steel , cast iron , copper , steel conduit , or EMT ( through Concrete Floor or Hollow -Core Floor ) inside Optional Gypsum Chase Wall
Max . 4 ” steel , cast iron , steel conduit or EMT ( 7 ” concrete ) ( AS = 0 ” to 1-1 / 2 ”)
Max . 2 ” copper pipe or tubing ( 7 ” concrete ) ( AS = 0 ” to 1-1 / 2 ”)
Max . 4 ” copper pipe or tubing ( 6 ” concrete ) ( AS = 0 ” to 1-7 / 8 ”)
Max . 1 ” copper , steel , cast iron , steel conduit or EMT ( 6 ” concrete ) ( AS = 0 ” to 2-7 / 8 ”)
Max . 4 ” steel , copper , conduit or EMT pipe ( AS = 3 / 4 ” to 3-1 / 2 ”)
Max . 18 ” steel or max . 4 ” copper pipe ( AS = 0 ” to 2-3 / 4 ”)
Max . 10 ” steel , max . 4 ” copper , conduit or EMT pipe ( AS = 1 / 2 ” to 7 / 8 ”) 1 or 2 Hr
Max . 12 ” steel , cast iron , max . 6 ” copper , conduit or max . 4 ” EMT in sleeve ( AS = 7 / 8 ” to 1 ”)
Max . 12 ” steel , max . 6 ” copper , conduit or max . 4 ” EMT ( AS = 3 / 8 ” to ½ ”)
Max . 8 ” steel or cast iron pipe or max . 4 ” conduit or EMT ( AS = 0 ” to 3 / 8 ”)
Max . 30 ” steel , cast iron , max . 6 ” copper , conduit or max . 4 ” EMT ( AS = 0 ” to 2-1 / 4 ”) ( Pipe may be at 45 º angle )
Max . 6 ” steel , copper , conduit or max . 4 ” EMT pipe in sleeve ( AS = 1 / 2 ” to 1-1 / 4 ”)
Max . 8 ” steel , cast iron , max . 6 ” conduit , max . 4 ” copper , EMT or max . 2 ” flexible steel conduit ( shaft wall ) ( AS = 1 / 4 ” to 1-5 / 8 ”)
Max . 8 ” steel , cast iron , max . 6 ” conduit , max . 4 ” copper , EMT or max . 2 ” flexible steel conduit ( shaft wall ) ( AS = 0 ” to 1-7 / 8 ”)
Max . 1 ” flexible steel conduit ( AS = 0 ” to ¾ ”)
Max . 2 ” steel conduit or EMT ( one or more ) ( AS = 0 ” to 3-3 / 8 ”)
Max . 8 ” steel , cast iron , 6 ” steel conduit , or 4 ” copper in sheet meta sleeve ( AS = 0 ” to 1-7 / 8 ”)
Max . 4 ” steel , cast iron , copper , conduit or EMT ( AS = 0 ” to 7-7 / 8 ”)
Max . 4 ” steel , cast iron , copper , conduit , or EMT ( AS = 0 ” to ½ ”)
Max . 30 ” steel , cast iron , max . 6 ” copper , conduit , or max . 4 ” EMT ( AS = 0 ” to 1-7 / 8 ”)
Max . 24 ” steel , cast iron , 6 ” copper , steel conduit , or 4 ” EMT ( AS = 0 ” to 7 / 8 ”) ( AS = 0 ” to 1-1 / 2 ”)
Max . 4 ” cast iron with stainless steel “ no-hub ” coupling ( AS = 0 ” to 1 ”)
Max . 8 ” steel , cast iron , max . 6 ” steel conduit , max . 4 ” copper or EMT ( AS = 0 ” to 7-7 / 8 ”)
CP 680-M CP 680-P CP 680-PX
Concrete Floors / Walls
System Number [ Similar FM Approved System ]
F--B1010
3 Hr ◼ ◼ CFS-DID C F-B-1026
2 Hr ◼ ◼ ◼
CFS-DID C / HC8 / HC10 / HC12
CP 681 w / mineral wool
CP 680-M CP 680-P CP 680-PX
CFS-CID M CFS-CID P
F-B-1029
F-B-1032
F-B-1033
F-B-1034
2 Hr ◼ FS-ONE MAX F-B-1035
2 Hr ◼ FS-ONE MAX HI / PHV-120
2 Hr ◼ FS-ONE MAX HI / PHV-120
2 Hr ◼ FS-ONE MAX HI / PHV-120
2 Hr ◼ FS-ONE MAX HI / PHV-120
2 Hr ◼ FS-ONE MAX W-J-1020
2 Hr ◼ FS-ONE MAX W-J-1021
FS-ONE MAX CP 601s CFS-S SIL GG
W-J-1028
4 Hr FS-ONE MAX W-J-1041
4 Hr FS-ONE MAX W-J-1042
1 or 2 Hr FS-ONE MAX W-J-1058
1 or 2 Hr ◼ FS-ONE MAX W-J-1067
4Hr FS-ONE MAX W-J-1068
1 or 2 Hr FS-ONE MAX W-J-1088
1 or 2 Hr FS-ONE MAX W-J-1089
1 Hr FS-ONE MAX W-J-1095
1 or 2 Hr Fire Foam W-J-1116
2 Hr
FS-ONE MAX CP 606
W-J-1222
1 or 2 Hr ◼ Fire Foam W-J-1123
1 or 2 Hr ◼ CP 606 W-J-1124
2 Hr ◼ CP 606 W-J-1128
1 or 2 Hr
CP601s CFS-S SIL GG
W-J-1168
2 Hr FS-ONE MAX W-J-1174
2 Hr ◼ CP 675T W-J-1175
CLICK CATEGORY INFO BELOW :
Blank Openings Metallic Penetrants Non-Metallic Pipes * Cables / Cable Trays Insulated Pipes
Miscellaneous Electrical ( Busway )
Miscellaneous Mechanical / Ducts
Mixed Penetrating Items *
Blank Openings Metallic Penetrants Non-Metallic Pipes * Cables Cable Trays Insulated Pipes
Miscellaneus Electrical ( Busway )
Miscellaneous Mecahnical / Ducts *
Mixed Penetrating Items *
Blank Openings
Metallic Penetrations
Non-Metallic Pipes * Cables Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Metallic Penetrations
Non-Metallic Pipes * Cables Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Bottom of Wall ( BW-S Series )
Continuity Head-of- Wall ( CJ-D Series )
Floor-to-Floor ( FF-D Series )
Floor-to-Wall ( FW-D Series )
Intertek Series ( ASTM E 1966 )
Head-of-Wall ( HW-D Series )
Head-of-Wall ( HW-S Series )
Wall-to-Wall ( WW-D Series )
Wall-to-Wall ( WW-S Series )
Perimeter Fire Barrier Joints ( Curtain Wall ) – ASTM E2307
Joints Steel-Framed Floors Wood-Framed Floors Framed ( Gypsum ) Walls Concrete Floors / Walls 6
Metallic Penetrants ( continued ) ➜