Firestop Selection Chart | Page 37

NEW
NEW
NEW
NEW
NEW
NEW
Penetrating Item ( s ) F-Rating T-Rating L-Rating Product
MISCELLANEOUS MECAHNICAL / DUCTS IN FRAMED ( GYPSUM ) WALLS * ( CONTINUED )
Max . 30 ” x 24 ” steel air or grease duct with 1-1 / 2 ” thick FireMaster ® Fast Wrap manufactured by Thermal Ceramics ( AS = 0 ” to 2 ”)
Max . 60 ” x 36 ” sheet metal duct ( w / o damper ) with max 2 ” thick
glass fiber duct insulation ( angles fastened through insulation )
( AS = 1 / 4 ” to 2-1 / 4 ”)
Max . 20 ” spiral would duct or 12 ” sheet metal duct ( w / o damper )
with 2 ” thick glass fiber duct insulation
( AS = 1 / 4 ” to 1 ”)
Max . 100 ” x 100 ” sheet metal duct ( w / o damper ) with 1-1 / 2 ” or
2 ” thick glass fiber duct insulation ( insulation split for angles )
( AS = 1 / 2 ” to 2 ”)
Max . 24 ” x 24 ” steel grease duct w / 1-1 / 2 ” FyreWrap Duct Wrap
manufactured by Unifrax
Max . 24 ” x 12 ” steel air or grease duct w / 1-1 / 2 ” duct wrap
manufactured by Unifrax
Max 20-1 / 8 ” x 42 ” x 5-3 / 4 ” Steel Electrical Box Membrane
through gypsum wall
1 or 2 Hr
◼
Max . 24 ” x 48 ” duct ( AS 1 / 4 ” to 1-1 / 4 ”)
Max . 12 ” ( 28 Ga ) Sheet metal duct ( AS 0 ” to 1-1 / 2 ”)
Max . 20 ” galvanized steel duct ( AS 0 ” to 1-1 / 2 ”)
Max . 20 ” galvanized steel duct ( AS 0 ” to 1-1 / 2 ”)
Max . 12 ” x 24 ” Sheet steel metal duct with 1-1 / 2 ” glass fiber insulation ( AS 1 / 4 ” to 1-1 / 2 ”)
Framed ( Gypsum ) Walls
System Number [ Similar FM Approved System ]
1 or 2 Hr FS-ONE MAX W-L-7121
1 or 2 Hr FS-ONE MAX W-L-7151
1 or 2 Hr FS-ONE MAX W-L-7153
1 or 2 Hr FS-ONE MAX W-L-7156
1 or 2 Hr ◼ FS-ONE MAX W-L-7157
1 or 2 Hr ◼ FS-ONE MAX W-L-7158
1 or 1-1 / 2 Hr
CFS-PA CP 617 FS-ONE MAX
W-L-7277
FS-ONE MAX FM 308
1 Hr FS-ONE MAX FM 311
1 Hr CP 606 FM 332
1 Hr CP 606 FM 337
1 Hr FS-ONE MAX FM 346
NEW Misc . small electrical boxes 3 / 4 Hr CP 617 Firestop Putty FM 598 NEW Misc . small electrical boxes 2 Hr CP 617 Firestop Putty FM 599 NEW Misc . small electrical boxes 2 Hr CP 617 Firestop Putty FM 600
NEW
Nom . 20 ” spiral wound steel duct ( min . 24 Ga .) ( AS 0 ” to 1-1 / 2 ”)
Misc . small electrical boxes
MIXED PENETRATING ITEMS IN FRAMED ( GYPSUM ) WALLS *
Max 3 ” EMT , max . 2 ” PVC ( c ), and cables ( AS varies )
Insulated or non-insulated steel , copper , conduit or EMT pipes , plastic pipe , cable tray or cables ( single or bundled ) ( AS varies )
Insulated or non-insulated steel , cast iron , copper , conduit or EMT pipes , plastic pipe , cable tray or cables ( single or bundled ) ( AS varies )
Insulated or non-insulated metallic ( AS varies )
Insulated or non-insulated steel , cast iron , copper , conduit or EMT pipes , flexible metal conduit or cables ( single or bundled ) ( AS varies )
Max . 6 ” steel tube ( 16 Ga ) and cables ( Translogic ) ( AS varies )
ABS fiber optic cable tray ( 12 ” x 4 ”), cable bundle ( various cables ), max . 2 ” fiber optic raceway ( PVC ) ( AS varies )
HVAC Line Set ( AS varies )
Insulated or non-insulated metallic , cable bundle ( AS varies )
Multiple 4 ” steel pipes , steel conduit , EMT and / or cable bundle ( AS = 0 ” to 1 ”)
1 Hr FS-ONE MAX FM 685
2 Hr ◼ Box insert FM 762
2 Hr ◼ FS-ONE MAX W-L-8004
1 or 2 Hr ◼ Firestop Block W-L-8013
1 , 2 , 3 or 4 Hr
1 , 2 , 3 , or 4 Hr
Firestop Block
Firestop Block
W-L-8014
W-L-8015
1 or 2 Hr ◼ Fire Foam W-L-8019
1 or 2 Hr FS-ONE MAX W-L-8023
1 or 2 Hr ◼ Firestop Block W-L-8035
2 Hr FS-ONE MAX W-L-8047
1 or 2 hr
Firestop Block w / Z-frame
W-L-8058
1 or 2 hr CP 675T W-L-8059
CLICK CATEGORY INFO BELOW :
Blank Openings Metallic Penetrants Non-Metallic Pipes * Cables / Cable Trays Insulated Pipes
Miscellaneous Electrical ( Busway )
Miscellaneous Mechanical / Ducts
Mixed Penetrating Items *
Blank Openings Metallic Penetrants Non-Metallic Pipes * Cables Cable Trays Insulated Pipes
Miscellaneus Electrical ( Busway )
Miscellaneous Mecahnical / Ducts *
Mixed Penetrating Items *
Blank Openings
Metallic Penetrations
Non-Metallic Pipes * Cables Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Metallic Penetrations
Non-Metallic Pipes * Cables Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Bottom of Wall ( BW-S Series )
Continuity Head-of- Wall ( CJ-D Series )
Floor-to-Floor ( FF-D Series )
Floor-to-Wall ( FW-D Series )
Intertek Series ( ASTM E 1966 )
Head-of-Wall ( HW-D Series )
Head-of-Wall ( HW-S Series )
Wall-to-Wall ( WW-D Series )
Wall-to-Wall ( WW-S Series )
Perimeter Fire Barrier Joints ( Curtain Wall ) – ASTM E2307
Joints Steel-Framed Floors Wood-Framed Floors Framed ( Gypsum ) Walls Concrete Floors / Walls 36
Mixed Penetrating Items * ( continued ) ➜