Firestop Selection Chart | Page 34

Penetrating Item ( s ) F-Rating T-Rating L-Rating Product
CABLES IN FRAMED ( GYPSUM ) WALLS ( CONTINUED )
Framed ( Gypsum ) Walls
System Number [ Similar FM Approved System ]
NEW Various cables 0-100 % visual fill 1 or 2 Hr ◼ CP 653 Speed sleeve FM 575 NEW Various cables Maximum 36 % fill 1 Hr CP 618 FM 596 NEW Various cables through cable transit system 2 Hr ◼ Cable Transit FM 666 NEW Various cables through cable transit system 2 Hr ◼ Cable Transit FM 667
NEW
NEW
CABLE TRAYS IN FRAMED ( GYPSUM ) WALLS
Aluminum or Cable Tray ( 24 ” x 6 ”) ( AS = 0 ” to 4 ”)
Aluminum or Steel Spine Cable Tray ( 18 ” x 6 ”) ( AS = 1 ” to 4-1 / 2 ”)
Aluminum Cable Tray ( 24 ” x 4 ”) ( AS = 0 ” to 5 ”)
Aluminum or Steel Cable Tray ( 24 ” x 4 ”) ( AS = 0 ” to 26 ”)
Max . 20 ” x 2 ” cable rack ( Telecom ) ( various cables ) ( AS = 0 ” to 3 / 4 ”)
Max . 25 ” x 2 ” cable rack ( max . qty 3 )( Telecom )( various cables ) ( AS varies ) 1 or 2 Hr
Max . 25 ” x 2 ” cable rack ( max . qty 6 ) ( Telecom )( various cables ) ( AS varies ) 1 or 2 Hr
Aluminum or Steel Cable Tray ( 24 ” x 6 ”) ( AS = 0 ” to 3 ”)
Aluminum or Steel Cable Tray ( 24 ” x 4 ”) ( AS = 0 ” to 26 ”)
Max . 20 ” x 2 ” wide open ladder steel cable tray , Max . 5 ” cable height installed .
Max . 18 ” x 6 ” aluminum cable tray , Max . 6 ” cable height installed .
INSULATED PIPES IN FRAMED ( GYPSUM ) WALLS
Max . 10 ” steel pipe with max . 2 ” glass fiber insulation ( Steel sleeve optional ) ( AS = 1-1 / 8 ”)
Max 2 ” steel or copper with max . ¾ ” AB / PVC insulation ( sleeved ) ( AS = 1-3 / 16 ” to 1-5 / 8 ”)
Max . 4 ” steel or max . 2 ” copper with max . ½ ” to 1 ” AB / PVC insulation ( AS = 0 ” to 1-1 / 2 ”)
Max . 12 ” steel , cast iron , max . 6 ” copper with 1 ”, 1-1 / 2 ”, or 2 ” glass fiber or max . 2 ” thick calcium silicate insulation ( AS = 0 ” to 1-7 / 8 ”)
Max . 12 ” steel or max . 6 ” copper pipe with max . 3 ” FOAMGLAS insulation with optional metal jacket
Max . 20 ” steel , max . 6 ” copper pipe with max . 3 ” glass fiber and mineral fiber insulation ( Steel sleeve optional )
Max . 6 ” steel , copper , conduit or EMT pipe with max . 1-1 / 2 ” glass fiber insulation in a sleeve ( AS = 1-1 / 4 ” to 1-1 / 2 ”)
Max . 12 ” steel or max . 6 ” copper pipe with max . 2 ” glass fiber insulation ( steel sleeve optional ) ( AS = 0 ” to 1-7 / 8 ”)
Max . 10 ” steel , cast iron or max . 4 ” copper pipe with max . 3 ” glass fiber insulation ( AS = 1 / 2 ” to ¾ ”)
Max . 10 ” steel pipe with max . 3 ” glass fiber insulation ( AS = 1 / 2 ” to ¾ ”)
1 or 2 Hr ◼ Firestop Block W-L-4011
1 or 2 Hr Firestop Block W-L-4019
1 or 2 Hr Fire Foam W-L-4034
1 or 2 Hr Firestop Block W-L-4038
1 or 2 Hr CP 675T W-L-4048
CP 675T Firestop Blocks w / Z frame
CP 675T Firestop Blocks w / Z frame
W-L-4049
W-L-4050
1 or 2 Hr FS-ONE MAX W-L-4060
1 or 2 Hr Firestop Block W-L-4081
1 Hr
CFS-BL CP 675T Firestop board CP 617
FM 519
2 Hr CFS-BL FM 661
1 or 2 Hr ◼
FS-ONE MAX w / Ret Collar
W-L-5025
2 Hr ◼ FS-ONE MAX W-L-5027
1 or 2 Hr ◼ FS-ONE MAX W-L-5028
1 , 2 or 3 Hr
◼ ◼ FS-ONE MAX W-L-5029
1 or 2 Hr FS-ONE MAX W-L-5046
1 or 2 Hr FS-ONE MAX W-L-5047
4 hr FS-ONE MAX W-L-5073
1 or 2 Hr FS-ONE MAX W-L-5096
2 Hr CP 648E / 1-3 / 4 ” W-L-5125
2 Hr CP 648E / 1-3 / 4 ” W-L-5126
CLICK CATEGORY INFO BELOW :
Blank Openings Metallic Penetrants Non-Metallic Pipes * Cables / Cable Trays Insulated Pipes
Miscellaneous Electrical ( Busway )
Miscellaneous Mechanical / Ducts
Mixed Penetrating Items *
Blank Openings Metallic Penetrants Non-Metallic Pipes * Cables Cable Trays Insulated Pipes
Miscellaneus Electrical ( Busway )
Miscellaneous Mecahnical / Ducts *
Mixed Penetrating Items *
Blank Openings
Metallic Penetrations
Non-Metallic Pipes * Cables Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Metallic Penetrations
Non-Metallic Pipes * Cables Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Bottom of Wall ( BW-S Series )
Continuity Head-of- Wall ( CJ-D Series )
Floor-to-Floor ( FF-D Series )
Floor-to-Wall ( FW-D Series )
Intertek Series ( ASTM E 1966 )
Head-of-Wall ( HW-D Series )
Head-of-Wall ( HW-S Series )
Wall-to-Wall ( WW-D Series )
Wall-to-Wall ( WW-S Series )
Perimeter Fire Barrier Joints ( Curtain Wall ) – ASTM E2307
Joints Steel-Framed Floors Wood-Framed Floors Framed ( Gypsum ) Walls Concrete Floors / Walls 33
Insulated Pipes ( continued ) ➜