Firestop Selection Chart | Page 30

Framed ( Gypsum ) Walls
CLICK CATEGORY INFO BELOW :
Penetrating Item ( s ) F-Rating T-Rating L-Rating Product
System Number [ Similar FM Approved System ]
Blank Openings
Metallic Penetrants
NON-METALLIC PIPES IN FRAMED ( GYPSUM ) WALLS * ( CONTINUED )
Max . 2 ” ABS , PVC , CPVC , FRPP or 1 ” PEX ( c , v ) ( AS = 5 / 16 ”)
Max . 8 ” PVC or CPVC ( c , v ) ( AS = 0 ” to 1-3 / 8 ”)
Max . 2 ” PVC or CPVC ( c ) ( AS = 0 ” to 5 / 8 ”)
Max . 6 ” PVC , CPVC , ABS or FRPP ( c , v ) ( AS varies )
1 or 2 Hr
CP 648E / 1 ” or CP648S
W-L-2235
1 or 2 Hr ◼ CP 648E / 1-3 / 4 ” W-L-2236
1 or 2 Hr ◼ ◼ FS-ONE MAX W-L-2244
4 Hr ◼ CP 643N W-L-2245
Non-Metallic Pipes *
Cables / Cable Trays
Insulated Pipes
Miscellaneous Electrical ( Busway )
Miscellaneous Mechanical / Ducts
Mixed Penetrating Items *
Blank Openings
Concrete Floors / Walls
Max . 4 ” PVC or CPVC ( c , v ) ( AS = 0 ” to 1 / 2 ”)
Max . 3 ” PVC or CPVC ( c , v ) ( AS = 3 / 16 ” to 1 / 4 ”)
Max . 4 ” PVC connecting to 4 ” Cast Iron ( w / No Hub Coupling ) ( Shaft Wall ) ( sleeved ) ( c , v ) ( AS varies )
Max . 9 ” PVDF ( c , v ) ( sleeved ) ( AS = 0 ” to ½ ”)
Max . 12 ” FRP pipe ( c , v ) ( sleeved ) ( AS = 0 ” to ½ ”)
Max . 6 ” Glass Pipe ( c , v ) ( AS = 0 ” to 1-1 / 4 ”)
Max . 4 ” ABS , PVC or CPVC ( c , v ) ( AS = 0 ” to ½ ”)
Max . 4 ” PVC , CPVC , or ABS ( c , v ) ( angled pipe ) ( AS = 0 ” to ¾ ”)
Max . 12 ” PVC or CPVC ( c , v ) ( AS = 0 ” to ½ ”)
Max . 4 ” ABS , PVC , or CPVC ( c , v ) ( AS = nom 3 / 8 ” to ½ ”)
Max . 2 ” FlowGuard Gold or Blazemaster CPVC ( c ) ( AS = 0 ” to 1-1 / 4 ”)
Max . 6 ” PVC , ABS or CPVC ( c , v ) ( AS varies )
Max . 4 ” PVC , ABS , FRPP or CPVC with optional coupling ( c , v ) ( AS = 0 ” to ½ ”)
Max . 2 ” ENT ( c ) ( AS = 1 / 4 ” to 3 / 4 ”)
Max . 2 ” ENT ( c ) ( AS = 3 / 16 ” to 5 / 16 ”)
Max . 3 ” PVC , ABS , or CPVC branch lines coming off of 6 ” cast iron soil stack within wall ( AS = 3 / 16 ” to 5 / 16 ”)
Max . 6 ” PVC , CPVC , or ABS ( c , v ) ( AS = 0 ” to ½ ”)
Max . 2 ” PVC or PP ( c , v ) ( AS = 0 ” to ¼ ”)
Max . 1-1 / 2 ” PVC , CPVC , RNC , or 1 ” PEX ( closed ) ( one or more ) ( AS = 0 ” to 1 ”)
Max . 4 ” diameter bundle of max . 1 ” PEX ( closed ) ( AS = 0 ” to 1 ’)
Max . 3 ” PVC , ABS , CPVC or RNC ( c , v ) ( U336 or U366 wall ) ( AS = 3 / 16 ” to 5 / 16 ”)
Max . 2 ” PVC , CPVC , or RNC ( c , v ) ( U336 or U366 wall ) ( AS = 0 ” to 5 / 8 ”)
Max . 4 ” PP ( c , v ) ( AS = 0 ” to ½ ”)
Max . 2 ” PVC , CPVC , PEX , RNC ( c , v ) ( AS = 0 ” to ½ ”)
Max . 1 ” PEX ( mq 6 ) ( c ) ( AS = ½ ” to1 ”)
Max . 2 ” PVC ( c , v ) with optional coupling ( AS = 0 ” to ½ ”)
1 or 2 Hr
1 Hr ◼
2 Hr
Ret . Collar w / FS-ONE MAX
CP 648E / 1 ” or 1-3 / 4 ”, or CP648S
FS-ONE MAX w / CP 643N
W-L-2251
W-L-2284
W-L-2292
1 or 2 Hr ◼ CP 648E / 1-3 / 4 ” W-L-2295
1 or 2 Hr ◼ CP 648E / 1-3 / 4 ” W-L-2315
1 or 2 Hr FSONE MAX W-L-2330
1 or 2 Hr ◼
CP 648E / 1 ” w / Ret Collar
W-L-2335
1 or 2 Hr CP 648E / 1-3 / 4 ” W-L-2340
1 or 2 Hr ◼ CP 648E / 1-3 / 4 ” W-L-2341
2 Hr ◼ CP 648E / 1-3 / 4 ” W-L-2344
1 or 2 Hr ◼ ◼ FS-ONE MAX W-L-2377
1 or 2 Hr ◼ CP 648S W-L-2406
1 or 2 Hr CP648E / 1 ” or 1-3 / 4 ” W-L-2411
3 or 4 Hr ◼ CP 618 W-L-2443
3 or 4 Hr ◼
1 or 2 Hr
1,2,3 or 4 hr
1 or 2 hr
◼
CP 648E FS-ONE MAX
CP648S FS-ONE MAX
CP648E / 1-3 / 4 ” w / Ret Collar
CP648E / 1 ” w / Ret Collar
W-L-2444
W-L-2445
W-L-2447
W-L-2453
1 or 2 hr FS-ONE MAX W-L-2466
1 or 2 hr FS-ONE MAX W-L-2467
2 Hr ◼
CP 648S FS-ONE MAX
W-L-2471
2 Hr ◼ FS-ONE MAX W-L-2472
1 or 2 Hr ◼ ◼ CP 643N W-L-2473
1 or 2 Hr ◼ FS-ONE MAX W-L-2474
1 or 2 Hr FS-ONE MAX W-L-2480
1 Hr ◼ FS-ONE MAX W-L-2482
Metallic Penetrants
Non-Metallic Pipes *
Cables
Cable Trays
Insulated Pipes
Miscellaneus Electrical ( Busway )
Miscellaneous Mecahnical / Ducts *
Mixed Penetrating Items *
Blank Openings
Metallic Penetrations
Non-Metallic Pipes *
Cables
Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Metallic Penetrations
Non-Metallic Pipes *
Cables
Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Bottom of Wall ( BW-S Series )
Continuity Head-of- Wall ( CJ-D Series )
Floor-to-Floor ( FF-D Series )
Floor-to-Wall ( FW-D Series )
Intertek Series ( ASTM E 1966 )
Head-of-Wall ( HW-D Series )
Head-of-Wall ( HW-S Series )
Wall-to-Wall ( WW-D Series )
Joints Steel-Framed Floors Wood-Framed Floors Framed ( Gypsum ) Walls
NEW
Max . 2 ” PP , 50mm Fusiother ( c , v ), or Polystar CT-White ( c ) ( AS = 0 ” to 5 / 8 ”)
Max . 4 ” PP ( SDR 11 ), Max 8 ” Aquatherm Greenpipe PP ( SDR 7.4 or 11 ), 8 ” Aquatherm Bluepipe PP ( SDR 9 or 11 ), 4 ” PP Orion Polystar Whiter ( SDR 11 , 9 , or 7.4 ), 4 ” Niron PP-RCT ( SDR 7.3 , 11 or 17 ) ( c , v ), 8 ” Niron PP-RCT ( SDR 7.3 or 11 ) ( c ), 8 ” Aquatecknik PP-RCT ( SDR 7.4 or 11 ) ( c ), 8 ” Uponor PP-RCT ( SDR 9 or 11 ) ( c ) AS = 0 ” to ½ ”) UL only
Max . 1 ” PEX ( bundled ) through CP 653 Speed Sleeve
1 or 2 Hr CP 643N W-L-2509
1 or 2 Hr
CP 648E / 1-3 / 4 ” w / Ret Collar
W-L-2510
1 or 2 Hr Speed Sleeve W-L-2537
Wall-to-Wall ( WW-S Series )
Perimeter Fire Barrier Joints ( Curtain Wall ) – ASTM E2307
29
Non-Metallic Pipes * ( continued ) ➜