Penetrating Item ( s ) F-Rating T-Rating L-Rating W-Rating Product
NON-METALLIC PIPES IN CONCRETE FLOORS / WALLS * ( CONTINUED )
Bundle of Max . 1 ” Pex ( c ) ( max qty = 6 ) ( hollow core ) ( AS = 1 / 8 “ to 1 / 2 ”)
Max . 6 ” PVC , CPVC , FRPP or ABS ( c , v ) ( 2-1 / 2 ” concrete over metal deck ) ( AS = 0 ” to 1-1 / 2 ”)
Max . 2 ” Optical Fiber Raceway ( c ) ( 2-1 / 2 ” concrete over metal deck ) ( AS = 1 / 2 ” to 1 ”)
Max . 6 ” PVC or CPVC ( c , v ) ( 2-1 / 2 ” concrete )
Max . 6 ” PVC or CPVC ( c , v )
Max . 2 ” PVC or CPVC ( c , v ) ( 2-1 / 2 ” concrete ) ( AS = 3 / 8 ” to 1 ”)
Max . 4 ” ABS or Nom . 6 ” FRPP ( c , v ) ( 2-1 / 2 ” concrete )
Max . 4 ” ABS or Nom . 6 ” FRPP ( c , v )
Max . 4 ” ABS , PVC , or CPVC ( c , v ) ( 2-1 / 2 ” concrete over metal deck ) ( AS varies )
Max . 3 ” ABS , PVC , or CPVC ( c , v ) ( 2-1 / 2 ” concrete over metal deck ) ( AS varies )
Nom . 4 ” PVC or ABS closet flange ( v )
Nom . 3 ” or 4 ” PVC or ABS closet flange ( v )
Nom . 4 ” ABS closet flange ( v ) ( 2-1 / 2 ” concrete ) ( AS = 1 / 4 ”)
Nom . 4 ” PVC closet flange ( v ) ( 2-1 / 2 ” concrete ) ( AS = 1 / 4 ”)
Max . 3 ” ABS , PVC , or CPVC ( c , v ) ( 2-1 / 2 ” concrete ) ( AS varies )
Max . 6 ” PVC and CPVC ( c , v )
Max . 2 ” PVC with Shower Drain ( v )
Tub Box with max . 1-1 / 2 ” PVC waste / overflow fittings
Tub Box with max . 1-1 / 2 ” PVC waste / overflow fittings
Multiple max . 2 ” PVC , CPVC or max . 1 ” ENT ( c )
Max . 6 ” FRPP , max . 4 ” PVDF , ABS , or PP ( c , v )
Max . 4 ” diam bundle of PEX tubing ( max . ½ ” diameter )
Max . 4 ” ABS , PVC , CPVC with pipe coupling ( 2-1 / 2 ” concrete over metal deck ) ( AS = 0 ” to 1-1 / 2 ”)
Max . 2 ” Flowguard Gold or Max . 3 ” Blazemaster ( c )
Max . 4 ” ABS , CPVC , or PVC transitioning to cast iron / steel through floor ( AS = 0 ” to 1-1 / 2 ”)
Nominal 2 ” diameter PVC drain ( shower )
Max . 6 ” PVC , CPVC , or RNC ( c , v )
Concrete Floors / Walls
System Number [ Similar FM Approved System ]
3 Hr ◼ FS-ONE MAX C-BJ-2041
2 Hr ◼ CP 643N F-A-2025
2 Hr FS-ONE MAX F-A-2046
2 Hr ◼ ◼
3 Hr ◼ ◼ ◼
CP 680-P CP 680-PX
CP 680-P CP 680-PX
F-A-2053
F-A-2054
2 Hr FS-ONE MAX F-A-2058
2 Hr ◼
3 Hr ◼ ◼
CP 680-P CP 680-PX
CP 680-P CP 680-PX
F-A-2065
F-A-2066
2 Hr CP 648E / 1-3 / 4 ” F-A-2067
2 Hr CP 648E / 1-3 / 4 ” F-A-2068
3 Hr ◼ CP 680-P 4 ” F-A-2071
3 Hr ◼
CP 680-P 3 ” or 4 ” CP 680-PX 3 ”
F-A-2072
2 Hr CP 643N F-A-2074
2 Hr CP 643N F-A-2075
3 Hr ◼ CP 648E / 1-3 / 4 ” F-A-2089
2 Hr ◼ ◼ ◼
2 Hr
CP 680-P CP 680-PX
CP 680-P CP 680-PX
F-A-2092
F-A-2093
3 Hr ◼ CP 681 F-A-2094
3 Hr CP 681 F-A-2095
2 Hr
2 Hr ◼ ◼
2 Hr
2 Hr
2 or 3 hr ◼
2-Hr ◼ ◼
Nom 1-1 / 2 ” or 2 ” PVC waster / averlflow fittings with
tub box ( 6 ” concrete )
2 Hr
◼
Max . 2 ” PVC , CPVC , or Greenpipe PP-R ( c , v ) with 1 ” or 2 ” glass fiber ( 4-1 / 2 ” concrete )
Max . 6 ” PVC , ABS , CPVC or FRPP ( 2-1 / 2 ” to 8 ” concrete ) ( optional steel sleeve )
Max . 2 ” PVC with shower / floor drain ( 4-1 / 2 ” to 8 ” concrete ) ( optional steel sleeve )
Max . 4 ” PP-R pipe © Auquatherm Greenpipe ( 4-1 / 2 ” concrete )
3 Hr ◼ ◼
4 Hr ◼ ◼
2 Hr ◼
CP 680-P CP 680-PX
CP 680-P CP 680-PX
CP 680-P CP 680-PX
CP 648E / 1-3 / 4 w / Ret Collar
CP680-P CP 680-PX
CP648E / Ret Collar w / FS-ONE MAX
Firestop Drain Flange CP 681 SD-FD
CP 680-P CP 680-PX
CP 681 CP 680-P 3 ” CP 680-PX 3 ”
CP 680-P CP 680-PX
F-A-2103
F-A-2141
F-A-2142
F-A-2143
F-A-2145
F-A-2154
F-A-2156
F-A-2166
F-A-2177
F-A-2205
3 Hr ◼ ◼ CFS-DID MD F-A-2213
2 Hr
3 Hr ◼
CFS-DID 3 ” C / HC8 / HC10 / HC12
CP 680-P CP-680-PX
F-A-2230
F-A-2270
CLICK CATEGORY INFO BELOW :
Blank Openings Metallic Penetrants Non-Metallic Pipes * Cables / Cable Trays Insulated Pipes
Miscellaneous Electrical ( Busway )
Miscellaneous Mechanical / Ducts
Mixed Penetrating Items *
Blank Openings Metallic Penetrants Non-Metallic Pipes * Cables Cable Trays Insulated Pipes
Miscellaneus Electrical ( Busway )
Miscellaneous Mecahnical / Ducts *
Mixed Penetrating Items *
Blank Openings
Metallic Penetrations
Non-Metallic Pipes * Cables Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Metallic Penetrations
Non-Metallic Pipes * Cables Insulated Pipes
Miscellaneous Mechanical / Duct Penetrations
Mixed Penetrating Items *
Bottom of Wall ( BW-S Series )
Continuity Head-of- Wall ( CJ-D Series )
Floor-to-Floor ( FF-D Series )
Floor-to-Wall ( FW-D Series )
Intertek Series ( ASTM E 1966 )
Head-of-Wall ( HW-D Series )
Head-of-Wall ( HW-S Series )
Wall-to-Wall ( WW-D Series )
Wall-to-Wall ( WW-S Series )
Perimeter Fire Barrier Joints ( Curtain Wall ) – ASTM E2307
Joints Steel-Framed Floors Wood-Framed Floors Framed ( Gypsum ) Walls Concrete Floors / Walls 11
Non-Metallic Pipes * ( continued ) ➜