Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 87

c. Every vestibule shall have a minimum dimension of not less than the required width of the corridor leading to it and a dimension of not less than one hundred eighty three centimeters (183 cm) in the direction of travel. 8. Mechanical Ventilation Smokeproof enclosures using mechanical ventilation shall comply with the following requirements: a. Vestibules shall have a dimension of not less than one hundred twelve centimeters (112 cm) in width and not less than one hundred eighty three centimeters (183 cm) in direction of travel. b. The vestibule shall be provided with not less than one air change per minute, and the exhaust shall be 150 percent of the supply. Supply air shall enter and exhaust air shall discharge from the vestibule through separate tightly constructed ducts used only for such purposes. Supply air shall enter the vestibule within one hundred fifty millimeters (150 mm) of the floor level. The top of the exhaust register shall be located not more than one hundred fifty millimeters (150 mm) below the top of the trap and shall be entirely within the smoke trap area. Doors, when in the open position, shall not obstruct duct openings. Controlling dampers shall be permitted in duct openings if needed to meet the design requirements. c. To serve as a smoke and heat trap and to provide an upward- moving air column, the vestibule ceiling shall be not less than five hundred ten millimeters (510 mm) higher than the door opening into the vestibule. The height shall be permitted to be decreased where justified by engineering design and field testing. d. The stair shall be provided with a dampered relief opening at the top and supplied mechanically with sufficient air to discharge at least 70.8 m3/min through the relief opening while maintaining a positive pressure of not less than 25 N/m2 in the stair, relative to the vestibule with all doors closed. 9. Stair Pressurization a. Smokeproof enclosures using stair pressurization shall use an approved engineered system with a design pressure difference across the barrier of not less than 12.5 N/m2 in sprinklered buildings, or 25 N/m2 in nonsprinklered buildings, and shall be capable of maintaining these pressure differences under likely conditions of stack effect or wind. The pressure difference across doors shall not exceed that which allows the door to begin to be 71