Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 86

3. Enclosure A smokeproof enclosure shall be enclosed from the highest point to the lowest point by barriers having 2-hour fire resistance ratings. Where a vestibule is used, it shall be within the 2-hour-rated enclosure and shall be considered part of the smokeproof enclosure. 4. Vestibule Where a vestibule is provided, the doorway into the vestibule shall be protected with an approved fire door assembly having a 1½-hour fire resistance rating, and the fire door assembly from the vestibule to the smokeproof enclosure shall have not less than a 20-minute fire resistance rating. Doors shall be designed to minimize air leakage and shall be self-closing or shall be automatic-closing by actuation of a smoke detector within three meters (3 m) of the vestibule door. New doors shall be installed in accordance with NFPA 105, Standard for the Installation of Smoke Door Assemblies. 5. Discharge Every smokeproof enclosure shall discharge into a public way, into a yard or court having direct access to a public way, or into an exit passageway. Such exit passageways shall be without openings, other than the entrance to the smokeproof enclosure and the door to the outside yard, court or public way. The exit passageway shall be separated from the remainder of the building by a 2-hour fire resistance rating. 6. Access For smokeproof enclosures other than those consisting of a pressurized stair enclosure complying with para (9) hereof, access to the smokeproof enclosure stair shall be by way of a vestibule or by way of an exterior balcony. 7. Natural Ventilation Smokeproof enclosures using natural ventilation shall comply with para (3) hereof and the following: a. Where access to the stair is by means of an open exterior balcony, the door assembly to the stair shall have a 1½-hour fire resistance rating and shall be self-closing or shall be automatic-closing by actuation of a smoke detector. Openings adjacent to the exterior balcony specified in the preceding paragraph shall be protected b. Every vestibule shall have a net area of not less than one and a half (1.5 m 2) of opening in an exterior wall facing an exterior court, yard, or public space not less than six meters (6 m) in width. 70