Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 78

lobby has no occupancy other than as a means of travel between elevators and street. 3. Revolving doors shall be equipped with means to prevent their rotation at too rapid a rate to permit orderly egress. L. Turnstiles 1. No turnstiles or similar device to restrict travel to one direction, or to collect fares or admission charges, shall be placed to obstruct any required means of egress, except that approved turnstiles not over ninety one centimeters (91 cm), which turn freely in the direction of exit travel, may be used in any occupancy where revolving doors are permitted. Turnstiles over ninety one centimeters (91 cm) shall be subject to the requirements for revolving doors. 2. No turnstiles shall be placed in any required exit, or barring the way of access thereto or travel therefrom, unless immediately adjacent or within six and one-tenth meters (6.1 m) there is a swinging door or gate opening freely in the direction of exit travel, an open passage serving the same general path of travel as the turnstile. 3. Turnstile shall be rated the same as revolving doors as regards units of exit width and rates of travel. M. Doors in Folding Partitions 1. When permanently mounted folding movable partition are used to divide a room into smaller spaces, a swinging door or open doorway shall be provided as a way of exit access from each such space. 2. The swinging door may be omitted and the partition may be used to enclose the space completely under the following conditions: a. The subdivided space shall not be used by more than twenty (20) persons at any time; b. The use of the space shall be under adult supervision; c. The partitions shall be so arranged that they do not extend across any aisle or corridor used as a way of access to the required exits from the floor; d. The partitions shall conform to the interior finish and other applicable requirements of this Chapter; and e. The partitions shall be an approved type, shall have a simple method of release, and shall be capable of being opened quickly and easily by inexperienced persons in case of emergency. 62