7. No FSIC shall be issued without the submission of Fire and Life Safety
Assessment Report 2 (FALAR 2) in accordance with Division 3 of this
Rule.
8. Upon approval or disapproval, the City/Municipal Fire Marshall having
jurisdiction shall issue an FSIC or NOD, as the case may be, and
endorse to BO/Owner, retaining one (1) copy for filing and properly
maintained for future reference.
SECTION 9.0.2.4
BUSINESS AND ROUTINE INSPECTION
A. Existing Building, Structure or Facility
The City/Municipal Fire Marshal having jurisdiction shall inspect all
buildings, structures or facilities to determine the presence of any fire
hazard, the types of occupancy, the prohibited acts being committed as
provided in Section 7 of Republic Act 9514, and to check or test the
required fire protective and/or warning systems. For this purpose, the
building owner or administrator shall make available to the FSI copies of all
plans, design calculations and specifications of the building as it was
actually built/ constructed, or in the absence of the same, copies of all
plans, design calculations and specifications of the building as it is at the
time of the inspection. The provisions of Section 9.0.2.2 apply when the
building, structure or facility will be repaired, renovated or modified as a
consequence of the inspection.
B. Industrial, Commercial or Business Operation
The City/Municipal Fire Marshal having jurisdiction shall cause the
inspection of premises of any industrial, commercial or business operations
and issue the necessary FSIC upon determination that fire safety measures
for storage, handling, and/or use of explosives or combustible, flammable,
toxic and other hazardous materials, as well as, for hazardous operations
or processes, have been complied.
C. Periodic Inspection by Fire Safety Inspectors
The City/Municipal Fire Marshal having jurisdiction shall cause the conduct
of periodic fire safety inspection of any building, structure, facility or
premises for the purpose of determining compliance with the provisions of
the Fire Code and this IRR. For this purpose, Inspection Order shall be
issued by the City/Municipal Fire Marshal having jurisdiction. Before
leaving the place inspected, report shall be prepared. Such inspection
Order and After Inspection Report shall conform to the herein prescribed
format, prepared in three sets and distributed as indicated. Format of the
After Inspection Report shall follow the approved fire safety standard
inspection checklist.