Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 52

7. No FSIC shall be issued without the submission of Fire and Life Safety Assessment Report 2 (FALAR 2) in accordance with Division 3 of this Rule. 8. Upon approval or disapproval, the City/Municipal Fire Marshall having jurisdiction shall issue an FSIC or NOD, as the case may be, and endorse to BO/Owner, retaining one (1) copy for filing and properly maintained for future reference. SECTION 9.0.2.4 BUSINESS AND ROUTINE INSPECTION A. Existing Building, Structure or Facility The City/Municipal Fire Marshal having jurisdiction shall inspect all buildings, structures or facilities to determine the presence of any fire hazard, the types of occupancy, the prohibited acts being committed as provided in Section 7 of Republic Act 9514, and to check or test the required fire protective and/or warning systems. For this purpose, the building owner or administrator shall make available to the FSI copies of all plans, design calculations and specifications of the building as it was actually built/ constructed, or in the absence of the same, copies of all plans, design calculations and specifications of the building as it is at the time of the inspection. The provisions of Section 9.0.2.2 apply when the building, structure or facility will be repaired, renovated or modified as a consequence of the inspection. B. Industrial, Commercial or Business Operation The City/Municipal Fire Marshal having jurisdiction shall cause the inspection of premises of any industrial, commercial or business operations and issue the necessary FSIC upon determination that fire safety measures for storage, handling, and/or use of explosives or combustible, flammable, toxic and other hazardous materials, as well as, for hazardous operations or processes, have been complied. C. Periodic Inspection by Fire Safety Inspectors The City/Municipal Fire Marshal having jurisdiction shall cause the conduct of periodic fire safety inspection of any building, structure, facility or premises for the purpose of determining compliance with the provisions of the Fire Code and this IRR. For this purpose, Inspection Order shall be issued by the City/Municipal Fire Marshal having jurisdiction. Before leaving the place inspected, report shall be prepared. Such inspection Order and After Inspection Report shall conform to the herein prescribed format, prepared in three sets and distributed as indicated. Format of the After Inspection Report shall follow the approved fire safety standard inspection checklist. 36