from one or more causes, such as open flames and hot surfaces, electrical arcs, sparks, or chemical reactions, shall be covered by the abovementioned manuals and shall comply with the applicable provisions of this IRR and/or in applicable cases by therein adopted Code of Practices prescribed by the manufacturer or internationally accepted standards. C. To address control and/or reduce the potential for ignition within plant, the following measures are prescribed: the 1. All entry sites within a plant, collection system, manholes, pumping stations and other facilities shall be properly protected from unauthorized entries. It shall be provided with appropriate security system and protection, by or in combination of security fencing, lockable gates/doors, at least two (2) hours fire rated compartmentation, posting of guards and/or installation of electronic video camera monitoring system as applicable, and made accessible only to authorized personnel and/or persons in authority. 2. Introduction of ignition sources at these sites as well as other parts of the plant shall be limited and regulated by an accepted life and safety procedural guidelines, supervised by a certified safety practitioner. As a general rule, introduction of ignition sources in these sites or areas shall be limited and adequate ventilation shall always be provided. Provided further, in cases where hotworkss or repair, rehabilitation, maintenance and other related activities that may introduce ignition are carried in a water or waste water treatment plant, an appropriate Fire Safety Clearance shall first be secured from City/Municipal Fire Marshal having jurisdiction. 3. Application of removal by vacuum or coverage with foam shall be necessary in event that a foreign combustible material enters the sewer system. 4. Chemicals and fuels shall always be stored in accordance with applicable provisions of this IRR and/or manufacturer’s instructions or international acceptable standards as adopted in the plant. Reactive chemicals shall always be stored separately with the foregoing reference to safety standards. In cases of having two or more degrees of safety, the most stringent degree of requirement shall prevail. SECTION 10.5.1.5 VENTILATION A. Ventilation rates for enclosed spaces containing used water or waste water exposed to the atmosphere shall be based on the calculated vaporization rate of the most volatile liquid anticipated to be present in the plant. B. In considering ventilation requirements, the designer shall base his calculations upon the surface area of channels, tanks, or other vessels 411