Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 406

SECTION 10.4.15.2 OPERATION A. Storage of Raw Materials and Finished Products 1. Tank storage of raw materials for organic coatings inside building shall be permitted only in storage areas at or above grade that have drainage which are detached from the processing area or cut off from the processing area by non-combustible construction having at least a two (2)-hour fire resistance rating. Openings shall be equipped with doors having two (2)-hour fire resistance rating. 2. Tank car and tank vehicle loading and unloading stations for Class I liquids shall be separated from the processing area, other plant buildings, and nearest line of adjoining property that may be built upon or public thoroughfare by a clear distance of not less than eight meters (8 m). Tank cars for flammable liquids shall be unloaded such that safety to persons and property is ensured. Tank vehicles for flammable and combustible liquids shall be loaded and unloaded in accordance with Section 10.3.4.2.1 of this IRR. 3. Loading and unloading structures and platforms for flammable and combustible liquids shall be designed and installed in accordance with this IRR. 4. Finished products of organic coatings shall be stored outside of the buildings, in separate building, or in separate room cut-off from the processing area by a non-combustible wall or partition having at least a two (2)-hour fire resistance rating. Openings shall be equipped with doors having two (2)-hour fire resistance rating. The storage of finished products shall be in tanks or in closed containers. 5. The nitrocellulose storage shall be in a separate building or in a room cut off by non-combustible construction having a fire resistance rating of at least two (2) hours and openings shall be equipped with doors having a minimum of two (2)-hour fire resistance rating. The nitrocellulose storage shall be used for no other purpose and shall be protected by a sprinkler system that provides a density of fourteen and three tenths liters per minute per square meter (14.3 l/min·m2) over the entire storage area. Electrical wiring and equipment installed shall be in accordance with the Philippine Electrical Code. 6. Nitrocellulose shall be stored in closed-containers. Barrels shall be stored in an upright position with the lid up and shall not be stored more than two (2) barrels high. Barrels or other containers of nitrocellulose shall not be opened in the main storage building but only at the point of use or other location intended for this purpose. The storage area shall be marked with a sign that states: “NITROCELLULOSE — FLAMMABLE SOLID — KEEP HEAT, SPARKS, AND FLAME AWAY” or 390