Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 402

F. Installation of Heating and Cooking Appliances 1. Kerosene and oil stove shall be equipped with a primary control furnished as an integral part of the appliance by the manufacturer to stop the flow of oil in the event of flame failure. 2. A conversion range oil burner shall be equipped with a thermal (heat- actuated) valve in the oil supply line, located in the burner compartment of the stove. 3. Oil burning appliance, small heating and cooking appliances shall be installed in accordance with NFPA 31 on Standards for the Installation of Oil Burning Equipment or with other internationally accepted standards. DIVISION 15. ORGANIC COATINGS SECTION 10.4.15.1 CONSTRUCTION A. Process Building 1. Manufacturing of organic coating shall be done on buildings without basements or pits and shall be constructed with non-load bearing walls and with fire resistive construction of noncombustible materials. 2. Organic coating manufacturing operations and operations incidental to or connected with organic coating manufacturing shall not be located in the same building with other occupancies. 3. Each organic coating factory located within fifteen meters (15 m) of adjoining property or structures or public thoroughfare shall have the exposing wall constructed as indicated below: Table 32: FIRE RESISTANCE RATING OF EXPOSING WALL OF ORGANIC COATING FACTORIES, BY DISTANCE FROM ADJOINING PROPERTY OR STRUCTURE Distance from adjoining property or structure of public thoroughfare Less than 3 meters 3 meters to 9 meters Over 9 meters but less than 15 meters Fire Resistance Rating of Exposing Wall At least 4 hours At least 3 hours At least 2 hours 4. Raw materials and finished stock storage buildings shall be limited to one (1) storey in height and either detached or cut-off from manufacturing buildings by non-combustible construction having a fire resistance rating of at least two (2) hours. Openings shall be equipped with fire doors of at least one and a half (1.5)-hours fire resistance rating. 386