Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 401

burners, such automatic devices shall be of a type specifically approved for use with the burner to which they are attached. 3. Each appliance fired by conversion oil burners, and each oil-fired unit, shall be provided with automatic limit controls which will prevent unsafe pressure or low water in a steam boiler or over-heating within a hot-water boiler, furnace or heater. 4. Limiting controls and low water shut-offs intended to prevent unsafe operation of heating equipment by opening an electrical circuit to the burner of shut-off device shall be so arranged as to effect the direct opening of that circuit whether the switching mechanism is integral with the sensing element or remote from same. 5. A water heater shall be provided with water pressure, temperature, and vacuum relief devices. Means shall be provided to prevent ship honing in any boiler or tank to which any circulating water heater is attached. 6. Electric motor-driven oil burners or a type not equipped with primary safety controls with integral oil pumps and electric motor-driven pump sets for use with such burner, not equipped with integral pumps, shall be provided with a motor controller incorporating no-voltage protection to be wired into the power supply to the motor. 7. In systems where either steam or air is used for atomizing the oil, or where air for combustion is supplied by a source which may be interrupted without shutting off the oil supply, the oil and atomizing or air supply shall be interlocked in a manner to immediately shut off oil supply upon failure of the atomizing or air supply. 8. Where automatically opened burners are used in installations equipped with force or induced draft fans or both, means shall be provided to immediately shut-off the oil supply upon fan failure. 9. Oil burners not equipped to provide safe automatic restarting after shut down shall require manual restarting after any control function to extinguish the burner flame. 10. Oil-fired appliances shall be installed in rooms that are large compared with the size of the appliance specifically approved for installation in a confined space such as an alcove or closet installation is in compliance with the approval. In alcove and closet installations, the clearances from the appliance to the walls and ceilings shall not be less than specified in the approval regardless of the type of construction. 385