Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 379

SECTION 10.4.7.5 AUTOMOBILE UNDERCOATING A. Operation 1. When approved by the City/Municipal Fire Marshal having jurisdiction, automobile undercoating spray operations conducted in areas having adequate natural or mechanical ventilation may be exempted from the requirements pertaining to spray finishing operations when using undercoating materials which are not more hazardous than kerosene (as listed by underwriters’ laboratories in respect to fire hazard rating 30-40), undercoating materials using only solvents having a flash point in excess of thirty seven and eight-tenths degrees Celsius (37.8°C), or no flames are within six thousand one hundred millimeters (6100 mm) while such operations are conducted. 2. Undercoating spray operations not conforming to this provision are subject to all applicable provisions of this IRR. SECTION 10.4.7.6 POWDER COATING A. Construction 1. Electrical equipment and other sources of ignition shall conform to the requirements of the Philippine Electrical Code. 2. Exhaust ventilation shall be sufficient to maintain the atmosphere below the lowest explosive limits for the material being applied. All non-deposited air-suspended powders shall be safely removed via exhaust ducts to the powder recovery cyclone or receptacle. Powders shall not be released to the outside atmosphere. 3. The provisions of internationally recognized standards for ovens and furnaces shall apply. 4. Electrostatic fluidized beds and associated equipment shall be of approved types. The maximum surface temperature of this equipment in the coating area shall not exceed sixty-five and six-tenths degrees Celsius (65.6°C). High voltage circuits shall be designed so as not to produce a spark of sufficient intensity to ignite any powder-air mixture nor result in shock hazard upon coming in contact with a grounded object under normal operating conditions. 5. Transformers, power packs, control apparatus and all other electrical portions of the equipment, with the exception of the charging electrodes and their connections to power, shall be located outside of the power coating area or shall otherwise conform to the requirements of this IRR. 363