Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 369

20. Unless the spray booth exhaust duct terminal is from a water-wash spray booth, the terminal discharge point shall be not less than one and eight tenths meters (1.80 m) from any combustible exterior wall or roof, nor discharge in the direction of any combustible construction or unprotected opening in any noncombustible exterior wall within seven and six tenths meters (7.60 m). 21. Exhaust ducts without dampers are preferred. However, if dampers are installed, exhaust ducts shall be maintained so that they will be in a full open position at all times the ventilating system is in operation. 22. Exhaust ducts shall have a clearance from unprotected combustible construction or material of not less than forty-five centimeters (45 cm). If combustible construction is provided with the following protection applied to all surfaces within forty-five centimeters (45), clearance may be reduced to the distances indicated in Table 30: Table 30: CLEARANCE REQUIRED FROM EXHAUST DUCTS AND UNPROTECTED COMBUSTIBLE CONSTRUCTION FOR SPRAY BOOTHS, BY TYPE OF PROTECTION USED Protection Used Gauge 28 sheet metal on Ā¼ -inch asbestos millboard. Gauge 28 sheet metal on 1/8-inch asbestos millboard space out 1 inch (2.54 cm) on noncombustible spacers. Gauge 22 sheet metal on 1-inch (2.54 cm) coated batts reinforced with wire mesh or the equivalent. Where ducts are protected with an approved automatic sprinkler system, the clearance required in section ā€œVā€ of this section may be reduced. Clearance required cm in 30.48 12 22.86 9 7.62 3 15.24 6 23. Air exhaust from spray operations shall not be directed so that it will not contaminate makeup air being introduced into the spraying area or other ventilating intakes. 24. Exhaust ducts shall be permitted to be round, rectangular, or other suitable shape. They shall be provided with doors, panels or other means to facilitate inspection, maintenance, cleaning and access to fire protection devices. 25. Containers supplying spray nozzles shall be of closed type or provided with closed metal covers. Containers not resting on floors shall be on non-combustible supports or suspended by wire cables. Containers supplying spray nozzles by gravity flow shall not exceed thirty eight liters (38ā„“) capacity. 26. All containers or piping to which a hose or flexible connection is attached shall be provided with a shut-off valve at the connection. 353