exhaust ducts, shall be of non-combustible material and readily removable or accessible on both sides for cleaning. Such plates shall not be located in the exhaust ducts. 8. Each spray booth having a frontal area larger than one square meter (1 m 2 ) shall have a metal deflector or curtain not less than eleven and four tenths centimeter (11.4 cm) deep installed at the upper outer edges of the booth over the opening. 9. Each spray booth shall be separated from other operations by not less than ninety one and five tenths centimeters (91.5 cm), or by a greater distance, or by such partition, wall, or floor/ceiling assembly having a minimum fire resistance of one (1) hour to reduce the danger of juxtaposition of hazardous operations as the City/Municipal Fire Marshal having jurisdiction may require, except for spray enclosures used for drying at elevated temperature. 10. Spray booths shall be installed that all portions are readily accessible for cleaning. A clear space of not less than ninety-one and five tenths centimeters (91.5 cm) on sides shall be kept clear of any storage or combustible materials. 11. When spraying areas are illuminated through glass panels or other transparent materials, only fixed lighting units shall be used as a source of illumination. Panels shall effectively isolate the spraying area from the area in which the lighting unit is located, and shall be of non- combustible material of such a nature or so protected that breakage will be unlikely. Panels shall be arranged so that normal accumulations of residue on the exposed surface of the panel will not be raised to a dangerous temperature by radiation or conduction from the source of illumination. B. Operation 1. Spraying operations, except electrostatic spraying operations, shall be designed, installed and maintained that the average air velocity from the spray impeller over the open face of the booth (or booth cross section spraying operations) shall not be less than thirty meters (30 m) per minute. Dry spray booths equipped with a filter roll that automatically advances when the air velocity is reduced to that specified in this paragraph shall be arranged to cause shutdown of spraying operations if the filter roll fails to advance automatically. Visible gauges or audible alarm devices shall be installed to indicate that the required air velocity is maintained. 2. Electrostatic spraying operations may be conducted with an air velocity over the open face of the booth of not less than eighteen meters (18 m) per minute or more depending on the volume of the 348