viii. No delivery of any flammable or combustible liquid shall be made into portable containers unless such container is of approved material and construction, having a tight closure with screwed or spring cover, so designed that the contents can be dispensed without spilling. The dispensing of flammable liquids into fuel tanks of vehicles or into a container shall at all times be under the supervision of a qualified attendant, except in service stations not open to the public. Such stations may be used by commercial, industrial, governmental or manufacturing establishments for fueling vehicles used in connection with their activities or operation. However, personnel of such establishments shall have knowledge and skills in dispensing flammable and combustible liquids. ix. Dispensing Services ix.a. Flammable and combustible Class I liquids shall be transferred from underground tanks by means of fixed pumps designed and equipped to allow control of the flow and to prevent leakage or accidental discharge. Supplemental means shall be provided outside of the dispensing device whereby the source of power may be readily disconnected in the event of fire or other related accidents. ix.b. Dispensing pumps that take suction at the top of the container shall be of approved type as UL and FM Listed or other equivalent internationally accepted standard. ix.c. Any device that operates through pressure within a storage tank or container shall not be allowed, unless the tank or container has been approved as pressure vessels. In no case shall air or oxygen pressure be used for dispensing flammable and combustible liquids. x. Pumps pressure delivery on service station shall be installed above grade level outside of buildings and shall be located not less than three meters (3 m) from line of adjoining property of noncombustible materials with at least one (1) hour fire resistance rating or from a property line that abut upon a public right-of-way or thoroughfare. x.a. Pumps installed above grade level shall be mounted on a concrete foundation and shall be protected against possible damage by vehicles. 269