Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 214

2. In buildings other than those complying with para (1) above, the travel distance, measured in accordance with Section 10.2.5.2 of this IRR, shall not exceed forty-six meters (46 m). G. Discharge from Exits Exit discharge shall comply with Section 10.2.5.2 of this IRR. H. Exit Signs and Lighting 1. Exit illumination shall be provided in accordance with Section 10.2.5.11 of this IRR. 2. Emergency lighting shall be provided in accordance with Section 10.2.5.11 of this IRR in any building where any one of the following conditions exists: a. The building is two (2) or more storeys in height above the level of exit discharge. b. The occupancy is subject to fifty (50) or more occupants above or below the level of exit discharge. c. The occupancy is subject to three hundred (300) or more total occupants. 3. Emergency lighting in accordance with 10.2.5.11 of this IRR shall be provided for all underground and limited access structures. 4. Means of egress shall have signs in accordance with Section 10.2.5.12 of this IRR. SECTION 10.2.14.3 PROTECTION A. Protection of Vertical Openings 1. Vertical openings shall be enclosed or protected in accordance with section 10.2.6.2of this IRR, unless otherwise permitted by the following: a. Unenclosed vertical openings in accordance with Section 10.2.6.2 of this IRR shall be permitted. b. Exit stairs shall be permitted to be unenclosed in two-storey, single tenant spaces that are provided with a single exit in accordance with Section 10.2.14.2 para ā€œDā€ (6) of this IRR. c. Unprotected vertical openings shall be permitted in existing buildings complying with all of the following: 198