and, in some cases, are impractical to eliminate. The City/Municipal Fire Marshal having jurisdiction might permit such dead ends to continue to exist, taking into consideration any or all of the following: i. Tenant arrangement ii. Automatic sprinkler protection iii. Smoke detection iv. Exit remoteness 3. Limitations on common path of travel shall be in accordance with the following: a. Common path of travel shall not exceed thirty meters (30 m) in a building protected throughout by an approved, supervised automatic sprinkler system in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems. b. Common path of travel shall not exceed thirty meters (30 m) within a single tenant space having an occupant load not exceeding 30 persons. c. In buildings other than those complying with para (3) (a) or (b) above, the common path of travel shall not exceed twenty three meters (23 m). d. It is recognized that common paths of travel exceeding the permitted limits exist and, in some cases, are impractical to eliminate. The authority having jurisdiction might permit such common paths of travel to continue to exist, taking into consideration any or all of the following: i. Tenant arrangement; ii. Automatic sprinkler protection; and iii. Smoke detection. iv. Exit remoteness F. Travel Distance to Exits 1. In buildings protected throughout by an approved, supervised sprinkler system in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems, the travel distance shall not exceed sixty one meters (61 m). 197