Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 184

Table 13: HAZARDOUS AREA OPERATION HAZARDOUS AREA DESCRIPTION SEPARATION/PROTECTION Areas not incidental to resident housing Boiler and fuel-fired heater rooms Central or bulk laundries > 9.3 m 2 Commercial cooking equipment Commissaries Employee locker rooms Hobby/handicraft shops Maintenance shops Padded cells Soiled linen rooms Storage rooms >4.6 m 2 in area but 9.3 m 2 in area storing combustible material Storage rooms >9.3 m 2 storing combustible materials Trash collection rooms 2 hours 1 hour 1 hour In accordance with 3.601 Smoke resistant Smoke resistant Smoke resistant Smoke resistant 1 hour 1 hour Smoke resistant 1 hour 1 hour Doors used to access the areas specified above shall meet the requirements for doors at smoke barriers for the applicable use condition. 2. Where smoke barriers are required, they shall limit the occupant load to not more than 200 residents in any smoke compartment and limit the travel distance to a door in a smoke barrier as follows: a. The distance from any room door required as exit access shall not exceed forty five meters (45 m). b. The distance from any point in a room shall not exceed sixty meters (60 m). 3. Any required smoke barrier shall be constructed in accordance with Section 10.2.6.9. Barriers shall be of substantial construction and shall have structural fire resistance. 4. Openings in smoke barriers shall be protected in accordance with Section 10.2.6.9 of this IRR, provided, that, there shall be no restriction on the total number of vision panels in any barrier. Provided, further, that sliding doors in smoke barriers that are designed to normally be kept closed and are remotely operated from a continuously attended location shall not be required to be self-closing. 5. Not less than fifty six hundredths square meters (0.56 m 2 ) of net area per occupant shall be provided on each side of the smoke barrier for 168