a smoke partition. Openings in walls or partition, used to allow the passage of light shall be wired glass set in metal frames. b. Every door opening therein shall be protected with a fire assembly as required in this Chapter, but not less than a self-closing or auto- matic closing, tight-fitting smoke assembly having a fire-protection rating of not less than twenty (20) minutes. c. Ducts penetrating atmospheric separation walls, partitions or floors, shall be equipped with an approved automatic-closing smoke damper when having openings into more than one atmosphere or atmospheric separation shall be maintained by an approved method of smoke control. d. All automatic-closing fire assemblies installed in the atmospheric separation shall be activated by approved smoke detectors. e. Janitor closets and storage rooms shall be enclosed by materials having one-hour fire resistance. Stages and enclosed platform shall be constructed in accordance with Division 8. D. Means of Egress 1. Each room occupied by more than three hundred (300) persons shall have one of its exit access through a separate means of egress. Where three (3) or more means of egress are required, not more than two (2) of them shall enter into the same means of egress. 2. Means of egress from interior rooms may pass through an adjoining or in intervening room, provided that the travel distance do not exceed those set forth in the succeeding paragraph entitled Travel Distance of Exit. Foyers and lobbies constructed as required for corridors shall not be construed as intervening rooms. Where the only means of egress from a room is through an adjoining or intervening room, smoke detectors shall be installed in the area of common atmosphere through which the means of egress must pass. The detectors shall actuate alarms audible in the interior room and shall be connected to the school fire alarm system. E. Travel Distance to Exits No point in a building shall be more than forty six (46) meters from an exit, measured in accordance with Section 10.2.5.2 of this IRR. F. Interior Finish Interior finish in flexible plan and open plan buildings shall be as follows: 142