Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 130

3. Application for Specific Hazards a. Selection of fire extinguishers for pressurized flammable liquids and pressurized gas fires type of hazard shall be made on the basis of recommendations by manufacturers of this specialized equipment. The system used to rate the effectiveness of fire extinguishers on Class B fires (flammable liquids in depth) is not applicable to these types of hazards. It has been determined that special nozzle design and rates of agent application are required to cope with such hazards. b. Selection of fire extinguishers for fires involving Class B materials in motion (three – dimensional Class B fires) such as pouring, running, or dripping flammable liquids and generally includes vertical as well as one or more horizontal surfaces shall be made on the basis of recommendations by manufacturers of this specialized equipment. c. Fire extinguishers for the protection of delicate electronic equipment shall be selected from either a carbon dioxide type or a halogenated agent type. G. Distribution of Fire Extinguishers 1. General Requirements a. Fire extinguishers shall be provided for the protection of both the building structure and the occupancy hazards contained therein. b. Required building protection shall be provided by fire extinguishers suitable for Class A fires. c. Occupancy hazard protection shall be provided by fire extinguishers suitable for such Class A, B, C, D, fire potentials as might be present. d. Fire extinguishers provided for building protection can be considered also for the protection of occupancies having a class a fire potential. e. Buildings having an occupancy hazard subject to Class B or Class C fires, or both, shall have a standard complement of Class A fire extinguishers for building protection, plus additional Class B or Class A fire extinguishers, or both. Where fire extinguishers have more than one letter classification (such as 2-A:20-B:C), they can be considered to satisfy the requirements of each letter class. 114