Fire Code of the Philippines Ebook - SafetySignsPH.com Fire Code of the Philippines eBook - SafetySignsPH | Page 120

b. In theaters, auditoriums and other assembly occupancies where the occupant load is more than one thousand (1,000), outlets shall be located on each side of any stage, on each side of the rear of the auditorium and on each side of the balcony. 4. Detailed Requirements a. Construction. Wet standpipes shall be installed and tested as required for the water distribution system within the building. b. Size. The size of the standpipes shall not be less than 64 mm (2 ½ in.) in diameter. c. Outlets. All interior wet standpipes shall be equipped with thirty eight millimeters (38 mm) valve in each storey, including the basement or cell roof of the building and located not less than ninety one centimeters (91cm) nor more than one hundred eighty two centimeters (182 cm) above the floor. d. Water Supply. The wet standpipe shall deliver not less than one hundred thirty two liters (132 ℓ) of water per minute at not less than one and eight-tenths (1.8) kilos per square centimeters residual pressures from each of any two outlets flowing simultaneously for thirty (30) minutes. When more than one interior wet standpipe is required in the building, such standpipes may be connected at their bases or highest points by pipes of equal size. Where combination standpipes are installed, the thirty eight millimeters (38 mm) outlet system may be supplied from the combination system with a fifty one millimeters (51 mm) connecting line. e. Pressure and Gravity Tanks. Pressure or gravity tanks shall have a capacity sufficient to furnish at least two hundred sixty five (265) liters of water per minutes for thirty (30) minutes. Other such tanks shall be located so as to provide not less than one and eight-tenths (1.8) kilos per square centimeters residual pressure from each of two (2) outlets flowing simultaneously for thirty (30) minutes. Discharge pipes from pressure tanks shall extend five (5) centimeters from and into the bottom of such tanks. All tanks shall be equipped with a manhole, ladder and platform, drainpipe, water pressure gauges, and a pressure relief valve. Each pressure tanks shall be tested in place after installation and proved tight at a hydrostatic pressure required, but not less than ten (10) kilogram per square centimeters. Where such tanks are used also for domestic purposes, the supply take off for such purposes shall be located above the required capacity of such tanks. Supply tanks shall be supported on non-combustible construction with not less than ninety one (91) centimeters clearances over the top and 104