221 |
Work
SER 5504
Commercial Energy Recovery Ventilator
The SER Series lowers demand on air conditioning systems. Air supplied from
outdoors enters through the energy recovery core where it transfers the heat
and moisture the incoming air to the outgoing air that was cooled and dried by
the building’s air conditioner. The air brought into the working area is cooled
and the humidity is reduced for maximum comfort. Reduces the load on an air
conditioner to save on cooling costs. This unit is designed for warmer, humid
climates with longer cooling seasons.
A preset defrost sequence is activated at an outdoor air temperature of 23ºF
and lower. During the defrost sequence, the supply blower shuts down & the
exhaust blower continues to ventilate for a few minutes. The unit then returns
to normal operation, and continues cycle.
Airflow up to 533 cfm @ 0.4” Ps
Push-pull configuration
External low voltage contacts
Dual service doors & reversible electrical box
External three position switch (Low/Standby/Medium)
Improved BMS integration
•
•
•
•
•
•
Maximum continuous airflow
in.wg
0.3” Ps
0.4” Ps
0.5” Ps
0.6” Ps
0.7” Ps
0.8” Ps
0.9” Ps
1.0” Ps
1.1” Ps
1.2” Ps
1.3” Ps
1.4” Ps
1.5” Ps
Supply air flow (high)
559
533
506
480
454
427
401
374
348
322
295
269
243
Exhaust air flow (high)
559
533
506
480
454
427
401
374
348
322
295
269
243
cfm
Energy performance
Supply temperature
Net Airflow
Sensible recovery efficiency
Latent recovery efficiency
Total recovery efficiency
F
cfm
%
%
%
35
560
67
39
57
35
420
70
46
62
O
Heating
95
560
64
28
42
95
Cooling
420
67
34
47
Specification data
SER 5504
fantech
Voltage /
phase
Rated
power
Max
amps
Average airflow @
0.4” Ps
V/~
Model
W
A
cfm
120 / 1
660
5.5
533
Connection
Defrost
cycle
Side
Auto
Shipping
weight
Item #
lbs
239
List price
USD
44925
3,325.00