483760 Edition II II | Seite 202

203 | Play SHR 8005R Commercial Heat Recovery Ventilators The SHR 8005R Commercial Heat Recovery Ventilation system (HRV) complements today's tight buildings. Fantech Heat Recovery Ventilators (HRV) are designed to supply air into a building while exhausting an equal amount of contaminated air to the outside. The aluminum heat exchange core transfers sensible energy between air steams resulting in tempering of the supply air and reduced loads on the HVAC system. During the defrost sequence, a motorized damper temporarily blocks the incoming fresh air stream so that the warm air from the building can circulate through the HRV. The exhaust blower shuts down and the supply blower switches into high speed to maximize the effectiveness of the defrost strategy. Airflow up to 772 cfm @ 0.4” Ps Push-push configuration External low voltage contacts Dual service doors & reversible electrical box External three position switch (Low/Standby/Medium) Improved BMS integration • • • • • • Maximum continuous airflow in.wg cfm 0.3” Ps 0.4” Ps 0.5” Ps 0.6” Ps 0.7” Ps 0.8” Ps 0.9” Ps 1.0” Ps 1.1” Ps 1.2” Ps 1.3” Ps 1.4” Ps 1.5” Ps Supply air flow (high) 802 772 743 713 684 654 625 596 566 537 507 478 449 Exhaust air flow (high) 802 772 743 713 684 654 625 596 566 537 507 478 449 Energy performance Supply temperature Net airflow Apparent sensible effectiveness F cfm % 35 690 63 35 518 68 95 690 47 95 518 49 Heating O Heating Cooling Specification data Model Voltage / phase V/~ W A cfm SHR 8005R 120 / 1 648 5.4 772 fantech Rated power Max amps Average airflow @ 0.4” Ps Connection Defrost cycle Shipping weight Side Recirculation 243 Item # lbs List price USD 40455-1 3,410.00