ZEMCH 2019 International Conference Proceedings April.2020 | Page 305

      Figure 5. Location of Temperature Sensors   To get more accurate measurement results, three temperature sensors were located at each point.    The temperature at each point was determined by averaging the three measured values.    The hot box facility was calibrated using polystyrene foam board whose thermal conductivity had  been acquired from heat flow meter apparatus test at an accredited laboratory designated by KOLAS,  Korea Laboratory Accreditation Scheme.  Tests were conducted with hot region temperature 20℃  and cold region temperature 0℃. The heat  flow rate from hot region to the cold region is determined from energy input to the hot region as in the  case with ASTM C 1363. The overall thermal transmittance was calculated after steady‐state conditions  have been achieved. Data were recorded three times every hour and averaged.    The overall thermal  transmittance (U) can be obtained from Equation (1).    State of The Art Insulation Technology for Zero Energy Buildings 294