ZEMCH 2019 International Conference Proceedings April.2020 | Page 179

Optimal Control of External Venetian Blinds  Considering Energy Performance  Minho Kang  1 , Hakjong Shin  1 , Sunhye Mun  2 , Younghoon Kwak  2 , Jung‐Ho Huh  2, *    Department of Architectural Enginnering, University of Seoul, Seoul, South Korea;  [email protected](M.K.); [email protected](H.S.)  2   Department of Architecture, University of Seoul, Seoul, South Korea; [email protected](S.M.);  [email protected](Y.K.)  *  Correspondence: [email protected]  1   Abstract: Recently, as an element technology for reducing building energy consumption, an external  venetian blind (EVB) has been attracting attention. In controlling EVB, optimal control considering  heating, cooling, and lighting is required. When applied in a real building, it is difficult to apply an  ideal control strategy easily due to problems such as complicated system and high cost. In this study,  three simple optimal control methods of EVB were presented for the south‐facing side of a business  building with external blinds. Using the Hooke‐Jeeves algorithm with optimization tool, GenOpt, the  yearly,  seasonally  and  monthly  optimal  angles  of  EVB  slats,  which  minimize  the  sum  of  cooling,  heating and lighting energy demands, were derived. In the case of monthly optimization, the energy  demand was the least calculated. It is mainly optimized to reduce cooling energy and lighting energy.    Keywords: External Venetian Blind; Slat Angle; Optimization; EnergyPlus; GenOpt                            Optimal Control of External Venetian Blinds Considering Energy Performance 168