Chillers and Heat Pumps | Absorption Chillers and Heat Pumps
YHAU-CL / CH-DXS Single Effect Double Lift Hot Water Driven Absorption Chiller
Cooling capacities from 176 kW to 2813 kW
Features
Flexible Operating Envelope The YORK YHAU-CL / CH-DXS Single Effect Double Lift Hot Water absorption chiller provides efficiency through the use of innovative technology . It is optimized to use low temperature waste heat - as low as 55 ° C where competitive offerings cannot operate . Common applications include comfort or industrial process cooling that use or recover waste heat from combined heat and power ( CHP ) systems , districs heating systems , industrial process or other available heat sources . The YHAU-CL / CH-DXS cooling capacity ranges from 176- 2,813 kW .
The YHAU-CL / CH-DXS has the unique ability to be used for applications where the
• Chilled water leaving temperature as low as 1 ° C .
• Cooling water temperature entering temperature as high as 37 ° C .
• Hot water temperature , driving heat source , entering temperature as high as 160 ° C and as low as 55 ° C .
• Hot water leaving temperature as low as 40 ° C .
Refrigerant cycle The YORK YHAU-CL / CH-DXS high efficiency single-effect double lift absorption refrigeration cycle uses water as the refrigerant and lithium bromide as the absorbent . It is the strong affinity and ease of separation that these two substances have for each other that makes the cycle work . The entire process occurs in hermetic vessels in a near complete vacuum .
96 YORK Air-Conditioning Products