Type II Industry Application Process Heating Application
With a Type II absorption heat pump , it is typical to have a heating COP of 0.47 , meaning 0.47 units of heat is obtained from the absorber with a 1.0 unit of driving heat source in the evaporator and generator . The 0.53 units of heat rejected in the condenser can be used for other process applications .
In this Type II absorption heat pump application , the jacket water of the gas engine at 90 ° C ( 194 ° F ) is the driving heat source . The heat pump delivers 137 ° C ( 279 ° F ) from the absorber section that can be flashed in a tank to produce low-pressure steam at 0.2 MPa ( g ) for process heating . A portion of the input heat is rejected through the condenser section and is used for other purposes in the facility .
|
|
|
|
|
|
Industrial Process |
Driving Heat Source Gas Engine Jacket Hot Water
Generator
Gas Engine
|
80 ° C
90 ° C
|
85 ° C / 185 ° F
Condenser
|
Evaporator |
Generator |
Absorber |
Heating
Hot Water 137 ° C / 279 ° F
Flash Tank
133 ° C / 271 ° F
0.2MPa ( g ) / 30 psig Steam
|
90 ° C / 194 ° F Heating COP 0.47
YORK Air-Conditioning Products 93