YORK_HVAC European catalogue_Mar. 2021_EN | Page 77

Minimum Driveline Maintenance and Costs of Ownership
YZ driveline features a single moving assembly suspended in a magnetic field that does not require lubrication .
With fewer moving parts than traditional oil- or refrigerant-lubricated drivelines longevity is enhanced and maintenance is reduced .
The chart compares driveline maintenance ( assuming other scheduled maintenance tasks are equal across centrifugal chillers )
Magnetic bearings and lubrication free designs mean :
• No scheduled compressor / motor teardowns ; components are designed to last the life of the chiller
• No required filter changes
• No complex lubrication system maintenance
Initial Chiller Cost + Cumulative Driveline Maintenance Cost
125-150 % of initial chiller cost
110-120 % of initial chiller cost
< 10 % of initial chiller cost
0 5 10 15 20 25 Years of Ownership
Initial Chiller Cost
YORK YZ Magnetic Bearing Chiller
Oil-lubricated Bearing Chiller
Refrigerant-lubricated Bearing Chiller
YZ are customized centrifugal units with job specific design . See below table as a reference , within Ecodesign capacity range .
Performances
YZ
900
1100
1300
1500
1600
1800
2000
Cooling capacity ( kW )
900
1100
1300
1500
1600
1800
2000
EER 5.99 5.65 6.30 6.00 6.27 6.40 6.10 SEER 8.40 9.00 9.50 9.17 9.00 8.90 9.00 ŋs , c % 333 357 377 364 357 353 357 Sound pressure 1m ( dB ( A )) 74 75 70 78 78 82 83
Ratings in accordance to Ecodesign , fixed water flow and variable outlet ( FW / VO ). For other Ecodesign calculations please contact your JCI Representative . The table above shows only a representative sample of performance points based on generic project operating conditions working with R1233zd refrigerant . For larger capacities up to 4200 kW , contact JCI Representative . The above data is based on Johnson Controls ’ selection software YORKworks 20.05b . Please refer to the latest version of the software for specific projects .
Technical data
YZ 900 1100 1300 1500 1600 1800 2000 Length mm 4347 4394 4446 5130
Dimensions
Width mm 1776 1880 2099 2356
Height mm 2244 2375 2515 2594 Refrigerant charge kg 230 303 319 364 353 462 452
1 . All dimensions are approximate . Certified dimensions , shipping and operating weights are available on request . 2 . Refrigerant charge quantity and unit weight will vary based on tube count .
YORK Air-Conditioning Products 77