Premium-efficiency VSD water-cooled screw compressor chiller

YVWH 115 to 445
Performances ( R1234ze )
YVWH 115 145 180 225 265 305 325 380 445 Cooling capacity kW 313.3 389.3 481.5 602.1 721.7 799.7 882.8 1033.0 1189.0
Optimized compressor ( Variable Vi )
Standard compressor ( Fix Vi )
Evaporator
Condenser
EER
6.23
6.41
6.19
6.41
6.25
6.25
6.07
6.24
6.13
SEER
8.61
8.81
8.85
9.13
9.31
9.31
9.68
10.01
9.82
ŋsc
341.44
349.57
351.17
362.27
369.36
369.36
384.34
397.44
389.9
EER
5.91
6.06
5.86
6.06
6.02
6.19
5.91
6.03
5.89
SEER
8.06
8.29
8.56
8.82
8.84
9.05
9.13
9.18
8.94
ŋsc
319.26
328.65
339.22
349.96
350.6
358.86
362.33
364.28
354.79
Pass
4
2
Flow rate
l / s
15.00
19.23
23.56
28.82
33.11
39.63
42.22
49.54
58.71
Piping dimension
mm
125
150
200
Pressure drop
kPa
44.5
53.6
53.3
51.6
43.0
37.2
19.6
27.1
32.8
Pass
4
2
Flow rate
l / s
17.56
22.42
27.55
33.61
38.75
46.18
49.53
57.87
68.74
Piping dimension
mm
125
150
200
Pressure drop
kPa
43.6
52.6
52.4
52.4
45.9
32.7
21.7
24.5
34.3
Refrigerant circuit
n .
1
Compressor qualtity
n .
1
Capacity control %
15-100 %
Refrigerant charge
kg
200
240
250
360
370
400
410
510
Sound pressure level ( 1m ) 1
dBA
78
80
82
84
80
85
87
89
91
Ratings in accordance to Ecodesign , variable water flow and variable outlet ( VW / VO ). Rated with YORKworks 20.05b . For other Ecodesign calculations or R134a information , please contact your JCI Representative .
1
Bare unit . Sound kit 1 or 2 are available for sound attenuation .
Technical data
YVWH
115
145
180
225
260
300
330
375
445
Length
mm
3118
3131
3154
3156
4807
4832
4873
Dimensions
Width
mm
1710
1797
1975
2005
1925
1988
2086
Height
mm
1966
1996
2124
2250
2300
2320
Operating weight kg
4387
5169
6350
6951
7834
8894
9306
9983
Soft Start
YVWH provides a soft start without current shock . The startup current will never be larger than the rating current , which benefits the customer with lower cost on associated equipment and smaller backup generator and quick start function in case of the shutdown due to power supply failure .
Displacement Power Factor ( DPF )
The Variable Speed Drive ( VSD ) design makes 0.95 high DPF achievable in standard YVWH models at all operating conditions . For traditional non-VSD designed screw chiller , the DPF will reduce when the cooling load goes down .
600
500
400
300
200
Solid state starter
Star-delta stater
1 0.9 0.8 0.7 0.6 0.5 0.4 0.3
YVWH
Traditional water-cooled screw chiller
100
YVWH
0.2 0.1
0
0
0 10 20 30 40 50
20 30 40 50 60 70 80 90 100
Time ( ms ) Capacity Load (%)
Manufacturer reserves the rights to change specifications without prior notice .
YORK Air-Conditioning Products 67