Super-high temperature water to water scroll heat pumps
YWH 302 to 2604
Nominal capacity
YWH LT / XL |
|
302 |
402 |
602 |
702 |
902 |
1202 |
1402 |
1804 |
2304 |
2604 |
Heating capacity ( EN14511 ) ( 1 ) |
kW |
38.8 |
46.0 |
58.4 |
70.3 |
88.4 |
109.9 |
136.5 |
176.9 |
219.5 |
273.2 |
Input power ( EN14511 ) ( 1 ) kW 8.2 9.4 11.8 14.8 18.8 23.1 27.9 37.2 45.7 55.3 COP ( EN14511 ) ( 1 ) W / W 4.73 4.85 4.93 4.76 4.70 4.75 4.88 4.75 4.80 4.94 Energy Class in low temperature ( 2 ) A ++ A ++ A ++ A ++ A ++ A ++ A ++ A ++ A ++ A ++ SCOP low temperature ( 2 ) kWh / kWh 4.85 5.00 5.16 5.00 5.08 5.17 5.36 5.29 5.38 5.56 ŋs , h low temperature ( 2 ) % 185.9 192.1 198.2 191.8 195.3 198.9 206.3 203.4 207.0 214.4 Energy Class in medium temperature ( 2 ) A ++ A ++ A ++ A ++ A ++ A ++ A ++ A ++ A ++ A ++ SCOP medium temperature ( 2 ) kWh / kWh 4.07 4.19 4.28 4.18 4.16 4.22 4.35 4.27 4.34 4.47 ŋs , h medium temperature ( 2 ) % 154.8 159.6 163.0 159.0 158.3 160.9 165.9 162.8 165.6 170.7 Power supply V / Ph / Hz 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 Maximum input current A 128.7 137.6 168.0 209.0 266.0 324.0 372.5 348.0 428.0 497.5 Peak current A 35.4 39.2 56.0 70.0 82.0 104.0 125.0 164.0 208.0 250.0 Compressors / Circuits n °/ n ° 2-1 2-1 2-1 2-1 2-1 2-1 2-1 4-2 4-2 4-2 Capacity steps n ° 2 2 2 2 2 2 2 4 4 4 Refrigerant R134a R134a R134a R134a R134a R134a R134a R134a R134a R134a Global warming potential ( GWP ) 1430 1430 1430 1430 1430 1430 1430 1430 1430 1430 Refrigerant charge Kg 2 2 3 3 4 5 6 8.5 10.5 13 Equivalent CO2 charge t 2.9 2.9 4.3 4.3 5.7 7.2 8.6 12.2 15.0 18.6 Sound power LS version ( 3 ) dB ( A ) -- -- -- -- -- -- -- 88 89 91 Sound pressure LS version ( 4 ) dB ( A ) -- -- -- -- -- -- -- 72 73 75 Sound power XL version ( 3 ) dB ( A ) 65 65 70 73 74 76 78 -- -- -- Sound pressure XL version ( 4 ) dB ( A ) 49 49 54 57 58 60 62 -- -- --
( 1 ) Heating : user water temperature 30 / 35 ° C , source water temperature 10 / 7 ° C . ( 2 ) Ratings in accordance with Ecodesign regulation 813 / 2013 , average climatic profile and variable water outlet temperature . ( 3 ) Sound power level in accordance with ISO 3744 . ( 4 ) Sound pressure level at 1 m from the unit in free field conditions in accordance with ISO 3744 .
Nominal capacity
YWH HT / XL |
|
302 |
402 |
602 |
702 |
902 |
1202 |
1402 |
1804 |
2304 |
2604 |
Heating capacity ( EN14511 ) ( 1 ) |
kW |
37.6 |
43.6 |
64.1 |
75.1 |
97.8 |
121.7 |
150.5 |
195.6 |
243.9 |
301.2 |
Input power ( EN14511 ) ( 1 ) kW 6.7 7.5 11.1 13.7 17.6 21.7 26.2 35.0 43.1 52.2 COP ( EN14511 ) ( 1 ) W / W 5.65 5.83 5.79 5.48 5.56 5.62 5.74 5.59 5.65 5.77 Energy Class in low temperature ( 2 ) A ++ A ++ A ++ A ++ A ++ A ++ A ++ A ++ A ++ A ++ SCOP low temperature ( 2 ) kWh / kWh 5.71 5.83 5.91 5.81 5.85 5.94 6.09 5.95 6.01 6.20 ŋs , h low temperature ( 2 ) % 220.2 225.3 228.2 224.5 226.0 229.4 235.6 230.0 232.4 239.9 Energy Class in medium temperature ( 2 ) A ++ A ++ A ++ A ++ A ++ A ++ A ++ A ++ A ++ A ++ SCOP medium temperature ( 2 ) kWh / kWh 4.62 4.73 4.78 4.76 4.67 4.74 4.85 4.73 4.79 4.91 ŋs , h medium temperature ( 2 ) % 176.9 181.1 183.2 182.2 178.7 181.5 186.1 181.0 183.6 188.3 Power supply V / Ph / Hz 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 400 / 3 / 50 Maximum input current A 111.4 128.7 167.1 208.3 267.9 324.8 372.9 353.7 430.4 498.7 Peak current A 32.8 35.4 54.2 68.6 85.8 105.6 125.8 171.6 211.2 251.6 Compressors / Circuits n °/ n ° 2-1 2-1 2-1 2-1 2-1 2-1 2-1 4-2 4-2 4-2 Capacity steps n ° 2 2 2 2 2 2 2 4 4 4 Refrigerant R134a R134a R134a R134a R134a R134a R134a R134a R134a R134a Global warming potential ( GWP ) 1430 1430 1430 1430 1430 1430 1430 1430 1430 1430 Refrigerant charge Kg 4 4 5 6 8 10 10 21 26 33 Equivalent CO2 charge t 5.7 5.7 7.2 8.6 11.4 14.3 14.3 30.0 37.2 47.2 Sound power LS version ( 3 ) dB ( A ) -- -- -- -- -- -- -- 88 89 91 Sound pressure LS version ( 4 ) dB ( A ) -- -- -- -- -- -- -- 72 73 75 Sound power XL version ( 3 ) dB ( A ) 65 65 70 73 74 76 78 -- -- -- Sound pressure XL version ( 4 ) dB ( A ) 49 49 54 57 58 60 62 -- -- --
( 1 ) Heating : user water temperature 30 / 35 ° C , source water temperature 10 / 7 ° C . ( 2 ) Ratings in accordance with Ecodesign regulation 813 / 2013 , average climatic profile and variable water outlet temperature . ( 3 ) Sound power level in accordance with ISO 3744 . ( 4 ) Sound pressure level at 1 m from the unit in free field conditions in accordance with ISO 3744 .
Manufacturer reserves the rights to change specifications without prior notice .
YORK Air-Conditioning Products 57