Chillers and Heat Pumps | Water-Cooled Chillers and Heat Pumps
YMWA / YMRA Water-cooled reversible heat pump with scroll compressor
Cooling capacities from 21 kW to 193 kW Heating capacities from 24 kW to 215 kW
Available versions
14 available YMWA sizes in three versions :
1 ) YMWA-CO : Cooling only 2 ) YMRA : Remote condenser 3 ) YMWA-HP : Reversible heat pump
Features
• Scroll compressors ( single or tandem )
• Higher EER and COP
• 2 different frames / configurations :
• 1 compressor / 1 circuit up to 45 kW
• 2 compressors / 1 circuit from 50 to 190 kW
• Reduced refrigerant charge
• Condensing pressure control
• “ Plug and Play ” units
Same cabinet w / o or with factory mounted hydrokit ( one or two pumps ). More compact and slim .
Nominal capacity and technical data
YMWA-CO 0020 0025 0030 0035 0040 0045 0050 0060 0075 0090 0120 0150 0170 0190
Cooling Capacity ( kW ) |
21.2 |
26.2 |
31.1 |
34.8 |
39.2 |
46.6 |
50.9 |
61.1 |
77.3 |
91.1 |
118.4 |
147.1 |
170 |
192.7 |
EER |
4.58 |
4.54 |
4.46 |
4.53 |
4.48 |
4.57 |
4.29 |
4.48 |
4.48 |
4.38 |
4.46 |
4.46 |
4.50 |
4.51 |
SEER |
5.58 |
5.60 |
5.45 |
5.50 |
5.35 |
5.83 |
6.13 |
6.38 |
5.95 |
6.70 |
5.90 |
6.13 |
6.08 |
6.20 |
ŋs , c |
220 |
221 |
215 |
217 |
211 |
230 |
242 |
252 |
235 |
265 |
233 |
242 |
240 |
245 |
Length / Width / Height ( mm ) |
821 / 455 / 1350 |
1210 / 850 / 1500 |
Operating weight ( kg ) |
162 |
182 |
179 |
185 |
191 |
214 |
352 |
371 |
392 |
411 |
597 |
666 |
701 |
745 |
YMRA 0020 0025 0030 0035 0040 0045 0050 0060 0075 0090 0120 0150 0170 0190 Cooling Capacity ( kW ) 21.2 26.2 31.1 34.8 39.2 46.6 50.9 61.1 77.3 91.1 118.4 147.1 170 192.7 Length / Width / Height ( mm ) 821 / 455 / 1350 1210 / 850 / 1500 Operating weight ( kg ) 144 164 166 166 172 172 332 344 365 376 558 612 643 674
YMWA-HP 0020 0025 0030 0035 0040 0045 0050 0060 0075 0090 0120 0150 0170 0190
Cooling Capacity ( kW ) |
21 |
26 |
30 |
34 |
38 |
46 |
50 |
59 |
76 |
89 |
115 |
145 |
166 |
186 |
Heating Capacity ( kW ) |
24 |
29 |
34 |
39 |
43 |
51 |
8 |
66 |
88 |
103 |
134 |
166 |
192 |
215 |
EER |
4.66 |
4.47 |
4.29 |
4.35 |
4.33 |
4.39 |
4.20 |
4.27 |
4.40 |
4.23 |
4.29 |
4.36 |
4.36 |
4.30 |
COP |
4.09 |
4.06 |
4.01 |
4.03 |
4.02 |
4.04 |
4.11 |
3.88 |
4.18 |
4.14 |
4.17 |
4.22 |
4.19 |
4.19 |
SCOP |
5.65 |
5.40 |
5.24 |
5.23 |
5.18 |
5.46 |
5.06 |
5.57 |
5.28 |
5.05 |
5.50 |
5.12 |
5.21 |
5.34 |
ŋs , h |
193 |
193 |
186 |
190 |
187 |
182 |
192 |
190 |
201 |
196 |
199 |
203 |
201 |
201 |
Length / Width / Height ( mm ) |
821 / 455 / 1350 |
1210 / 850 / 1500 |
Operating weight ( kg ) |
165 |
187 |
184 |
190 |
195 |
219 |
360 |
379 |
403 |
422 |
610 |
683 |
718 |
762 |
Net values at Eurovent nominal conditions : YMWA-CO : Standard Eurovent LCP / W / AC conditions in cooling mode : evaporator EWT / LWT 12 ° C / 7 ° C , condenser EWT / LWT 30 ° C / 35 ° C YMRA : Evaporator EWT / LWT 12 ° C / 7 ° C , condensing temperature 40 ° C YMWA-HP : Standard Eurovent LCP / W / AC conditions in cooling mode : evaporator EWT / LWT 12 ° C / 7 ° C , condenser EWT / LWT 30 ° C / 35 ° C YMWA-HP : Standard Eurovent LCP / W / AC conditions in heating mode : evaporator EWT / LWT 10 ° C / 7 ° C , condenser EWT / LWT 40 ° C / 45 ° C Ecodesign figures are calculated following fixed water and variable outlet approach ( FW / VO ). For other Ecodesign calculations , please contact your JCI representative . SEER and SCOP calculated according to EN14511 and EN14825 ηs calculated according to Ecodesign regulation for chillers comfort cooling and heating ( 813 / 2013 , 2016 / 2281 ). The above data is based on Johnson Controls ’ selection software YORKworks 20.05b . Please refer to the latest version of the software for specific projects