Dimensions and hydraulic connections
Closed-loop ( CL ) configuration models
YVFA 1239 CL
All dimensions in mm . Drawings not in scale .
Application flexibility (*) example of selections
YVFA |
0539 |
0709 |
0889 |
1009 |
1069 |
1239 |
1419 |
1589 |
Mechanical Cooling capacity ( kW ) |
577 |
684 |
898 |
1034 |
1158 |
1232 |
1517 |
1664 |
Full Load Efficiency ( EER ) - Mechanical 2.8 2.78 2.78 2.88 2.73 2.77 2.46 2.32 Part Load Efficiency ( SEPR ) - Mechanical 6.02 5.98 6.06 6.24 5.59 5.5 5.54 5.5 Sound power level ( dBA ) - Mechanical 103 104 106 106 106 107 107 109 Total Temperature Free-Cooling (° C ) -0.5 -0.4 -1.5 -1.5 -2.7 -2.1 -3.3 -4.5
Cooling Capacity for Open-Loop configuration at : entering / leaving chilled fluid temperature 16 ° C / 10 ° C ( 30 % Ethylene Glycol ), ambient temperature 35 ° C . Sound Pressure according to Eurovent conditions . (*) YVFA is a tailor and tune chiller . Its peformance will be factory-adjusted to match the exact site requirements based on the specific project operating conditions . The table above shows only a representative sample of performance points based on generic project operating conditions working with R513a refrigerant . For R134a information contact your JCI Representative . For tailored and tuned performance based on your specific project requirements , and for more information , please contact your Johnson Controls representative . The above data is based on Johnson Controls ’ selection software YORKworks 21.0a . Please refer to the latest version of the software for specific projects .
Technical data
YVFA |
0539 |
0709 |
0889 |
1009 |
1069 |
1239 |
1419 |
1589 |
Length |
mm |
6280 |
7397 |
8514 |
9631 |
9631 |
10748 |
11864 |
Dimensions |
Width |
mm |
2242 |
2243 |
|
Height |
mm |
2405 |
2404 |
Operating weight kg |
7394 |
8504 |
10396 |
11842 |
11884 |
12900 |
14131 |
17140 |
Refrigerant charge kg |
172 |
164 |
216 |
246 |
262 |
282 |
365 |
368 |
YORK Air-Conditioning Products 47