YORK_HVAC European catalogue_Mar. 2021_EN | Page 29

Air-cooled scroll compressor chiller

YLAA 0195 to 0517
Nominal capacity
YLAA
0195 *
0221
0262
0286
0301
0350
0392
0442
0457
0517
Cooling capacity ( kW )
195
211
246
274
299
347
376
434
469
528
EER
3.17
3.40
3.24
2.79
3.17
3.07
3.09
3.07
3.09
3.10
SEER
4.28
4.65
4.40
4.14
4.44
4.36
4.46
4.58
4.70
4.57
ŋs , c
168
183
173
162
174
171
175
180
185
180
Sound power level dB ( A )
87
83
83
84
85
86
86
87
87
87
Net values at Eurovent nominal conditions : Cooling capacities in kW given for 7 ° C water leaving temperature ∆t 5 ° C and 35 ° C ambient temperature . Ecodesign figures are calculated following fixed water and variable outlet approach ( FW / VO ). For other Ecodesign calculations , please contact your JCI representative . (*) All models with R454B refrigerant using EC fans ( except size 0195 ) and Compressor Sound Blankets . The above data is based on Johnson Controls ’ selection software YORKworks 20.05b . Please refer to the latest version of the software for specific projects .
Technical data
YLAA 0195 0221 0262 0286 0301 0350 0392 0442 0457 0517 Length mm 2911 3690 4807
Dimensions
Width mm 2242 2254
Height mm 2508 Operating weight kg 1706 1721 1852 1853 2170 2339 2508 3343 3481 3615
YLAA Pump Kit
• Fixed or VSD water pump
• Single or Dual water pump
• Two option levels - basic and full featured - for maximum flexibility
• More impeller size options for better match to customer requirements
• New , smaller pump motors suitable for primary-secondary systems
Inlet to evaporator
Customer inlet
Customer outlet
Manufacturer reserves the rights to change specifications without prior notice .
YORK Air-Conditioning Products 29