YORK_HVAC European catalogue_Mar. 2021_EN | Page 21

Heat pump scroll compressor

YLPB 0345 to 0650
Nominal capacity
YLPB
0345
0430
0525
0575
0650
Cooling capacity ( kW )
336
413
479
559
629
EER 3.00 2.93 2.88 2.95 2.99 SEER 4.36 4.55 4.47 4.53 4.51 ηs , c 172 179 176 178 178 Heating capacity ( kW ) 344 427 514 575 653 COP 3.07 3.07 3.03 2.99 3.01 SCOP 3.53 3.52 3.54 3.47 3.47 ŋs , h 138 138 139 136 136 Sound Power Level ( dBA ) 96 96 97 98 99
Net values at Eurovent nominal conditions : Cooling capacities in kW given for 7 ° C water leaving temperature ∆t 5 ° C and 35 ° C ambient temperature . Heating capacities in kW given for 45 ° C water leaving temperature and 7 ° C ambient temperature . SCOP calculated according to EN14511 and EN14825 . ηs calculated according to Ecodesign regulation for heating ( 813 / 2013 ). Ecodesign figures are calculated following fixed water and variable outlet approach ( FW / VO ). For other Ecodesign calculations , please contact your JCI representative . The above data is based on Johnson Controls ’ selection software YORKworks 20.05b . Please refer to the latest version of the software for specific projects .
Technical data
YLPB 0345 0430 0525 0575 0650 Length mm 4721 5839 6958
Dimensions
Width mm 2242
Height mm 2391 Operating weight kg 3793 4043 4210 4747 5495
High Efficiency Cooling Mode
Additional Energy Savings in Heating Mode
Efficiency
Running cost ( Euros / kWh of useful heat )
Heat Pump efficiency ( ESEER )
Annual energy cost
3.5
-0.035
4.3
- € 27,500
4.2
19 %
- € 25,000
4.0
7 %
- € 22,500
3.7
3.5
3.2
- € 20,000
- € 17,500
3.0 2.5 2.0 1.5 1.0 0.5
3 %
-0.033
-0.031
-0.029
-0.027
3.0
Typical 10-15 year old Heat Pump
Typical Heat Pump today
YLPB
- € 15,000
0.0
Typical Boiler today
YLPB
-0.025
500 kW unit , 3000 operating hours , energy rate = 0.1 EUR / kWh Energy Rate : Electricity 0.1 EUR / kWh ; Gas 0.03 EUR / kWh
Operation limits
Carbon footprint in Heating Mode
Heating mode
Cooling mode
Efficiency
CO2 Emmissions ( g CO2 / kWh )
Ambient temperature (° C )
40 35
25
15
7
Ambient temperature (° C )
50 46 40
30
20
3.5 3.0 2.5 2.0 1.5
23 %
-250
-200
-150
-100
-4
-15 30 35 40 45 50 55
Leaving water temperature (° C )
10
0 0 2 4 6 8 10 12 14 16 18 20
Leaving water temperature (° C )
1.0
0.5
0.0
Typical Boiler today
YLPB
-50
-0
Manufacturer reserves the rights to change specifications without prior notice .
YORK Air-Conditioning Products 21