YORK_HVAC European catalogue_Mar. 2021_EN | Page 15

Air cooled Scroll DC Inverter reversible heat pump

YMPA 045 to 260
Technical features
Model
Performance
Refrigerant
Compressor
Air side heat exchanger
Water side heat exchanger
Dimensions and weight
YMPA
45 65 80 100 130 160 200 230 260
Cooling capacity
kW
44
60
78
99
122
159
188
221
254
EER
2.86
2.78
3.10
3.00
2.94
3.12
3.04
3.09
3.06
SEER
4.38
4.50
4.43
4.24
4.42
4.24
4.28
4.17
4.34
ηs , c
172
177
174
167
174
167
168
164
171
Heating capacity
kW
46
55
84
91
126
161
182
224
245
COP
2.96
2.99
3.12
3.05
2.83
3.08
3.06
3.05
3.07
SCOP
3.43
3.45
3.40
3.37
3.39
3.53
3.53
3.40
3.32
ηs , h
134
135
133
132
132
138
138
133
130
Sound power level STD / LN ( cooling )
dB ( A )
81 / 75
83 / 78
82 / 78
84 / 79
85 / 81
87 / 82
88 / 83
88 / 83
89 / 84
Refrigerant circuits
#
1
1
2
2
2
3
3
4
4
Refrigerant charge ( R410A )
kg
9.5
12.3
17.6
20.5
22.8
29.5
32
43.3
46
Type
DC Scroll Inverter + Scroll
Capacity steps
%
Stepless ( Inverter )
Quantity
2
2
3
3
4
5
6
7
8
Fan motor type
EC motor
Fans quantity
1
1
2
2
2
3
3
4
4
Working ambient temp . cooling mode
-18 ~ 48 ° C
Working ambient temp . heat . mode
-15 ~ 25 ° C
Type
Plate Heat Exchanger
Unit water volume ( w / o pump kit )
l
9
10
11
14
15
27
29
32
34
Pump Type
Fixed / Variable Speed Drive Pump
Variable Speed Drive Pump
Nominal water flow
l / s
2.1
2.9
3.7
4.7
5.8
7.4
9.1
10.5
11.9
Pressure drop ( cooling )
kPa
32
25
27
30
36
25
32
41
38
Working range water leaving temp . cooling
-12 ~ 20 ° C
Working range water leaving temp . heating
25 ~ 55 ° C
Height ( w / o pump kit )
mm
2440
2500
Width ( w / o pump kit )
mm
1200
3050
Depth ( w / o pump kit )
mm
1500
2240
Operating weight ( w / o pump kit )
kg
587
610
893
920
999
1,922
2,003
2,235
2,316
Net values at Eurovent nominal conditions : Cooling capacities in kW given for 7 ° C water leaving temperature ∆t 5 ° C and 35 ° C ambient temperature . Heating capacities in kW given for 45 ° C water leaving temperature and 7 ° C ambient temperature . SEER and SCOP calculated according to EN14511 and EN14825 . ηs calculated according to Ecodesign regulation for chillers comfort cooling and heating ( 813 / 2013 , 2016 / 2281 ). Ecodesign figures are calculated following fixed water and variable outlet approach ( FW / VO ). For other Ecodesign calculations , please contact your JCI representative . The above data is based on Johnson Controls ’ selection software YORKworks 20.05b . Please refer to the latest version of the software for specific projects .
Perfect solution for rental application
• Ambient operating range in cooling mode from -18 to 48 ° C
• Outstanding minimum leaving fluid temperature , down to -12 ° C
• Power quick connector CEE17 for main power ( 400 / 3 / 50 , 3P + G ) and 220V compressor heater ( in chiller panel )
• Water quick connector Camlock ( EN14420-7 )
• Gate valves for water inlet / outlet connections
• Condenser coil : Gold fin pre-coating and wire mesh around coil
• Chiller IP54 and control panel IP55
• Low Sound compressor enclosure
• Available ESP up to 200 kPa at standard conditions
• Rental Panel ( by request )
• Connected Service Kit ( by request )
• Perfect solution for Ice-Rink rental applications Note : please contact your JCI representative for getting your special quotation
Advanced Control Made Easy
To help maximize efficiency and keep you in control , the YORK AMICHI Series comes standard with integrated Smart Equipment . This technology allows the equipment to connect seamlessly to building controls like our world-class Verasys system , where smart-enabled equipment can self-identify and interoperate .
Remote Access via Internet
Verasys Smart Building Hub
Plug and play experience
Smart Chiller / Heat Pump
Smart Air Handling Unit
Verasys Zone Controller
Room Module
Smart Fan Coil Unit
Manufacturer reserves the rights to change specifications without prior notice .
YORK Air-Conditioning Products 15