YORK Modular Air Handling Units
Type 5
PHE - Plate Heat Exchanger Unit
FA Damper |
G3 and F8 filters |
Heat Recovery |
|
M6 filters |
|
RA damper |
EXH damper |
Return / Extract fan |
Drain pan |
Heating coil |
Drain pan |
Cooling coil |
Supply fan |
For European Union countries heat recovery systems as per European Legislation EU / 1253 / 2014 should be implemented .
Model
Width B
Dimensions [ mm ]
Height H
Length L
Weight [ kg ]
Airflow range nominal m 3 / s m 3 / h
Heat Recovery [%]
Power Input [ kW ]
YMA ( S51 ) 0970H-0950W 950 1 940 5 100 1 292 0.6 2 160 76.9 0.68 A + YMA ( S52 ) 0970H-1500W 1 500 1 940 5 350 1 832 1.2 4 320 75.8 1.274 A + YMA ( S53 ) 1570H-1550W 1 550 3 140 6 200 2 746 2.4 8 640 73.9 2.581 A + YMA ( S54 ) 1570H-2150W 2 150 3 140 7 250 3 694 3.6 12 960 75 3.575 A + YMA ( S55 ) 1970H-2500W 2 500 3 940 7 550 5 004 5.4 19 440 73.2 4.946 A + YMA ( S56 ) 1970H-3150W 3 150 3 940 8 050 6 273 7.2 25920 73 6.685 A + YMA ( S57 ) 1970H-4050W 4 050 3 940 8 900 8 231 9.6 34 560 74 8.726 A + YMA ( S58 ) 1970H-4900W 4 900 3 940 9 300 8 186 12 43 200 76.5 10.562 A + YMA ( S59 ) 1970H-5900W 5 900 3 940 8 500 8 843 13.5 48 600 77.3 11.146 A +
Panel : Galvanised Steel 0.6mm - Frame : Aluminum PR55TT - Fire rated Rockwool insulation 100 kg / m3 density - Filter M6 / G4 + F7 - TT : T2 - TB : TB2 Casing Strength : D1 ( M ) - Casing Air Leakage + PA700 : L2 ( M ) - Casing Air Leakage -400Pa : L1 ( M )
EUROVENT Class 2016
AHU N ยบ 05.02.314 Range : YMA
Manufacturer reserves the rights to change specifications without prior notice .
YORK Air-Conditioning Products 131