YORK_HVAC European catalogue_Mar. 2021_EN | Page 129

Inline Outside Air or Mixing Supply Air Unit with Return Fan

YORK Modular Air Handling Units

Type 3
Inline Outside Air or Mixing Supply Air Unit with Return Fan
M6 filters
EXH damper
RA damper
FA damper
RA damper
Return / Extract fan
G4 + F7 filters
Heating coil Drain pan Cooling coil Supply fan
For European Union countries heat recovery systems as per European Legislation EU / 1253 / 2014 should be implemented .
Model
Width B
Dimensions [ mm ]
Height H
Length L
Weight [ kg ]
Airflow range nominal m 3 / s m 3 / h
Power Input [ kW ]
YMA ( S31 ) 0970H-0950W 950 970 5 800 969 0.6 2 160 0.551 A + YMA ( S32 ) 0970H-1500W 1 500 970 5 800 1 278 1.2 4 320 1.054 A + YMA ( S33 ) 1570H-1550W 1 550 1 570 6 200 1 806 2.4 8 640 2.009 A + YMA ( S34 ) 1570H-2150W 2 150 1 570 6 800 2 349 3.6 12 960 2.938 A + YMA ( S35 ) 2250H-2150W 2 150 2 250 6 800 2 884 5.4 19 440 4.568 A + YMA ( S36 ) 2250H-2750W 2 750 2 250 7 100 3 560 7.2 25 920 6.005 A + YMA ( S37 ) 2860H-2850W 2 850 2 860 8 200 5 039 9.6 34 560 7.668 A + YMA ( S38 ) 2860H-3450W 3 450 2 860 7 300 5 134 12 43 200 9.806 A + YMA ( S39 ) 2860H-4050W 4 050 2 860 7 800 6 143 13.5 48 600 10.238 A +
Panel : Galvanised Steel 0.6mm - Frame : Aluminum PR55TT - Fire rated Rockwool insulation 100 kg / m3 density - Filter M6 / G4 + F7 - TT : T2 - TB : TB2 Casing Strength : D1 ( M ) - Casing Air Leakage + PA700 : L2 ( M ) - Casing Air Leakage -400Pa : L1 ( M )
EUROVENT Class 2016
AHU N ยบ 05.02.314 Range : YMA
Manufacturer reserves the rights to change specifications without prior notice .