YORK_HVAC European catalogue_Mar. 2021_EN | Page 118

YORK
YVAG012RSE30-0AM
2015 811 / 2013
Chillers and Heat Pumps

Regulation 813 / 2013

Space Heaters

SCOP η s , h
Published regulation 813 / 2013 affects all Heat Pumps ( both air and water cooled ) with a rated heating output below 400 kW ( measured at -10 ° C ambient )
It relates to units used for space heating application that supply hot water and covers two sub-categories based on the leaving water temperature : medium temperature and low temperature .
YORK heat pump units affected by this regulation are classified as Low Temperature because heating outlet fluid temperature can not be supplied at 52 ° C ( measured at -7 ° C ambient ). “ Low-temperature application ” means an application where the heat pump space heater delivers its declared capacity for heating at an indoor heat exchanger outlet temperature of 35 ° C
SCOP- Seasonal Coefficient of Performance
Ecodesign regulation 813 / 2013 introduces a new indicator called Seasonal Coefficient of Performance ( SCOP ), which is the ratio between the annual heating demand and the annual electrical input energy over the entire heating season .
SCOP is calculated using standard EN14825 , which takes the following into account :
• Seasonal efficiency while the compressor is running ( SCOPon )
• Electrical consumption when the compressor is not running : crankcase heater , standby or OFF mode
• Backup heater required to achieve the defined heating design load
SCOP takes into account the energy efficiency achieved at each outdoor temperature of an average climate weighted by the number of BIN hours for each of those temperatures .
400
TOL * A Tbiv ** B C D
350
100
Number of operating hours at specific ambient temperatures
300
250
200
150
100
50
0
80
60
40
20
0
Unit load (%)
* TOL = Operation limit temperature ( maximum -7 ° C ).
** Tbiv = ’ bivalent temperature ’ ( T biv ) means the outdoor temperature declared by the manufacturer for heating at which the declared capacity for heating equals the part load for heating . Maximum T biv is + 2 ° C .
-17
-20 -19 -18
-15
-16
-14 -13 -12 -11
-9
-10
-8
-7
-6
-4
-5
-3
-2
-1
1
0
2
3
4
5
6
7
8
9
11
10
12
13
14
15
2 % of the time
Unit runs 23 % of the time
Unit runs 75 % of the time
Outdoor temperature (° C )
The number of operating hours for a heat pump covered by SCOP is 4910h ( 56 % of the total year hours ).
Efficiency requirements set by REGULATION 813 / 2013 – Heat Pumps
Regulation 813 / 2013 sets seasonal energy efficiency in Eta s heat ( η s h ). This value expresses SCOP in terms of primary energy and it makes it possible to compare the energy efficiency of units using different energy sources .

ƞ s , h

(%) = 1 / CC x SCOP-∑F i

CC = Conversion Coefficient = 2.5
∑F i = Correction Factor
Air source heat pumps = 3 % Water source heat pumps = 8 %
Heat Pumps
Tier 1 ( Oct 2015 ) Tier 2 ( Oct 2017 ) η s , h % SCOP η s , h % SCOP Air to water low temperature heat pumps < 400 115 2.95 125 3.20 Water to water low temperature heat pumps < 400 115 3.08 125 3.33
Energy Labelling Regulation 811 / 2013
Heat Pumps with capacities below 70 kW are classified by the European Energy Labelling regulation 811 / 2013 with the objective to inform to the end-user about which is the efficiency level of the heat pump adquired .
A ++
A + A B C D E F G
7 kW kW kW
35 ° C
A +
69 dB
118 YORK Air-Conditioning Products