YORK ® AIR-CONDITIONING PRODUCTS
Large ACTIVA Rooftop
ARC-ARH 100 to 175 AB
Technical features
Cooling only models
ARC 100 AB ARC 125 AB ARC 150 AB ARC 175 AB
Net cooling capacities kW 108.1 121.8 149.3 169.0
Power input kW 34 41 59 64
4.95 4.58 3.72 3.29
195.0 180.1 145.7 128.8
SEER
ηs,c
Working range (full load / partial load) *
°C
Heat pump models
7°C ~ 46°C / -10°C ~ 52°C
ARH 100 AB ARH 125 AB ARH 150 AB ARH 175 AB
Net cooling capacities kW 108.1 121.8 149.3 169.0
Power input in cooling kW 34 41 59 64
Heating capacities (1) kW 104.6 118.4 147.0 167.0
Power input in heating kW
SCOP
ηs,h
Working range (full load / partial load) *
33 37 53 61
3.58 3.44 3.44 3.44
140.2 134.5 134.6 134.5
°C
-10°C ~ 46°C / -10°C ~ 52°C
Common characteristics
400V / 3 / 50Hz
Power supply
Main switch A
Main cable Nbr. x mm 2
Cable to thermostat Nbr. x mm 2
100 125 160 200
3 x 35 3 x 50 3 x 50 3 x 70
31 000
10 x 0,22
Number of circuits / Compressor type
Airflow
Evaporator fan
at nominal airflow Power input
Nett dimensions
2 (tandem) / 4 x scroll
m 3 /h 19 000 21 000 27 000
kW 3.0 3.3 8.3
9.1
Height mm 2 142 2 142
Length mm 4 036 5 085
Depth mm 2 250
2 250
Nett weight ARC kg 1 737 1 744 2 074 2 090
Nett weight ARH kg 1 765 1 772 2 135 2 150
All the data are at EUROVENT conditions with 400V/3+N/50Hz.
Cooling : Entering indoor coil temp. 27°C / 19°C WB and outdoor temperature 35°C - Heating : Entering indoor coil temp. 20°C and outdoor temperature 7°C / 6°C WB
(1) Add indoor fan motor consumption to know total heating capacity.
* With Premium kit (full load / partial load): -10°C ~ 50°C / -10°C ~ 52°C
Codes
Cooling only models
Heat pump models
ARC 100 AB ARC 125 AB ARC 150 AB S661852400 S661852420 S661852450 S661852480
ARH 100 AB ARH 125 AB ARH 150 AB ARH 175 AB
S661852403 S661852423 S661852453 S661852483
Thermostat
to be ordered separately
DPC-1
Manufacturer reserves the rights to change specifications without prior notice.
181