York HVAC Catalogue 2018 EN 2019 EN | Page 156

Performance at JOHNSON CONTROLS test conditions* Technical Characteristics YC-OPA: direct expansion air conditioners with air cooled or water condensers and up-flow air supply Models 71 141 211 251 301 302 361 461 422 512 662 852 932 94.4 Performances Total cooling capacity kW 8.0 14.8 21.4 26.4 33.2 31.1 37.9 47.9 43.7 54.7 68.9 86.8 Sensible cooling capacity kW 7.6 13.1 21.4 25.7 32.0 31.1 37.9 47.4 43.7 53 66.9 75 85 3.72 3.46 3.36 3.28 3.17 3.36 3.49 3.57 3.42 3.4 3.41 3.46 3.63 EER Airflow m 3 /h 2.200 3.200 7.000 7.000 8.700 8.700 14.500 14.500 14.500 14.500 17.900 17.900 20.700 Sound pressure level dB(A) 51 57 56 57 60 60 59 59 59 59 60 60 61 Lenght mm 750 750 860 860 1.410 1.410 1.750 1.750 1.750 1.750 2.300 2.300 2.640 Depth mm 601 601 880 880 880 880 880 880 880 880 880 880 880 Height mm 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 Net weight kg Dimensions & weight 180 210 270 270 320 340 440 450 450 500 640 660 860 Free Cooling ¡ ¡ ¡ ¡ l l ¡ ¡ ¡ ¡ l l ¡ Two Sources ¡ ¡ l ¡ l l ¡ ¡ ¡ ¡ l l ¡ * Performance refers to: R410a refrigerant; condensing temperature 45°C; incoming air 24°C-45%Rh; water 7/12°C; external static pressure 30 Pa. The declared performance does not take into account the heat generated by fans, which must be added to the system thermal load. EER (Energy Efficiency Ratio) = total cooling capacity / compressors power consumption + fans power consumption (air cooled condensers excluded). Sound levels at a 2 m distance, in a free field, as per UNI EN ISO 3744:2010. Technical Characteristics YC-UPA: direct expansion air conditioners with air cooled or water condensers and down-flow air supply Models 71 141 211 251 301 302 361 461 422 512 662 852 932 94.4 Performances Total cooling capacity kW 8.0 14.8 21.4 26.4 33.2 31.1 37.9 47.9 43.7 54.7 68.3 86.8 Sensible cooling capacity kW 7.6 13.1 21.4 25.7 32.0 31.1 37.9 47.4 43.7 53 66.9 75 85 3.72 3.46 3.36 3.28 3.17 3.36 3.49 3.57 3.42 3.4 3.41 3.46 3.63 EER Airflow m 3 /h 2.200 3.200 7.000 7.000 8.700 8.700 14.500 14.500 14.500 14.500 17.900 17.900 20.700 Sound pressure level dB(A) 51 57 56 57 60 60 59 59 59 59 60 60 61 Lenght mm 750 750 860 860 1.410 1.410 1.750 1.750 1.750 1.750 2.300 2.300 2.640 Depth mm 601 601 880 880 880 880 880 880 880 880 880 880 880 Height mm 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 1.990 Net weight kg Dimensions & weight 180 210 270 270 320 340 440 450 450 500 640 660 860 Free Cooling ¡ ¡ ¡ ¡ l l ¡ ¡ ¡ ¡ l l ¡ Two Sources ¡ ¡ l ¡ l l ¡ ¡ ¡ ¡ l l ¡ * Performance refers to: R410a refrigerant; condensing temperature 45°C; incoming air 24°C-45%Rh; water 7/12°C; external static pressure 30 Pa. The declared performance does not take into account the heat generated by fans, which must be added to the system thermal load. EER (Energy Efficiency Ratio) = total cooling capacity / compressors power consumption + fans power consumption (air cooled condensers excluded). Sound levels at a 2 m distance, in a free field, as per UNI EN ISO 3744:2010. 156