LASER & LOW BODY Fan Coil Units
0.6 to 9.7 kW
Technical features
Model
LOW BODY: YLVR, YLIVR
Sizes
max
Total cooling capacity [kW]
Sensible cooling capacity [kW]
Water flow in cooling [l/h]
(1)
(1)
(1)
Pressure drop in cooling [kPa]
Heating capacity 2 pipes [kW]
Water flow in heating 2 pipes [l/h]
Pressure drop in heating 2 pipes [kPa]
Heating capacity 4 pipes [kW]
Water flow in heating 4 pipes [l/h]
Pressure drop in heating 4 pipes [kPa]
(1)
(2)
(2)
(2)
(3)
(3)
(3)
Air flow [m3/h]
Sound power level [dB(A)]
Sound pressure level [dB(A)]
(4)
110 112 114 216 218
0.98 1.21 1.87 2.74 3.23
med 0.81 1.02 1.61 2.35 2.81
min 0.64 0.80 1.37 1.84 2.37
max 0.90 1.09 1.62 2.32 2.71
med 0.73 0.92 1.39 1.97 2.34
min 0.56 0.71 1.15 1.54 1.95
max 166 207 318 519 614
med 139 175 274 442 531
min 109 137 233 346 446
10.2
max 2.5 3.5 8.4 7.1 med 1.9 2.6 6.5 5.4 7.9
min 1.3 1.8 5.0 3.6 5.9
max 1.18 1.53 2.22 3.16 3.78
med 0.95 1.29 1.9 2.67 3.25
min 0.76 1.02 1.58 2.18 2.71
max 204 265 384 595 717
med 163 224 328 501 612
min 130 176 273 405 506
max 2.5 4.2 9.3 7.3 11.8
med 1.7 3.2 7.1 5.4 8.9
min 1.2 2.1 5.2 3.7 6.4
max 1.12 1.79 1.87 2.54 3.83
med 0.93 1.54 1.65 2.22 3.37
min 0.77 1.25 1.42 1.89 2.88
max 98 157 165 224 338
med 81 135 145 196 297
min 68 109 125 167 254
max 1.8 4.8 6.5 11.8 5.9
med 1.3 3.7 5.2 9.4 4.7
min 1.0 2.5 4.0 7.1 3.6
max 243 317 432 606 754
med 181 253 352 488 616
min 136 185 279 377 486
max 47 50 53 51 55
med 41 44 49 45 50
min 34 38 42 39 43
max 37 40 44 42 46
med 31 35 39 36 41
min 25 29 33 29 34
Power input [W] max 46 48 57 61 76
Absorbed current [A] max 0.21 0.21 0.25 0.27 0.33
Power supply [V-ph-Hz]
Dimensions
230 / 1 / 50 + E
Height mm 430 430 430 430 430
Width mm 648 773 898 1023 1148
Depth mm 254 254 254 254 224
(1) Room temperature 27°C d.b., 19°C w.b. - Water temperature 7/12 °C
(2) Room temperature 20°C - Water inlet temperature: 45/40°C
(3) Room temperature 20°C - Water inlet temperature: 65/55°C.
(4) Sound pressure level in a 100 m3 room, at 1.5 m distance and riverberating time of 0.3 s. max = speed 2, med = speed 3, min = speed 5 when using selection software
Manufacturer reserves the rights to change specifications without prior notice.
120